background image

A/C

 – Air conditioning also 

referred to as A/C. A system 

or device for reducing the 

temperature and humidity, in 

a space.

AHAM

 – Acronym for Association 

of Home Appliance Manufacturers. 

AHAM produces the official rating 

for dehumidifiers. 

BTU

 – British Thermal Unit. A 

single BTU is the amount of energy 

required to cool or heat a pound of 

water one degree Fahrenheit. 

Condenser

 – The unit used to 

condense a substance from a 

gaseous state to liquid by cooling 

it. Condensers are generally 

recognized as heat exchangers. In 

the case of air conditioners they 

extract the inside heat from the 

interior of the air conditioner to 

the outside air. Often referred to as 

“the outdoor unit.”

Dehumidifier

 – Also called, 

dehums. Dehumidifiers remove 

humidity and are used to keep a 

rooms humidity levels in check. 

Maintaining correct humidity will 

ensure a healthy crop. Too much 

humidity will cause molds, rot and 

devastate your crop.

Digital Inverter Compressor

 – 

A digitally controlled compressor 

that converts AC voltage to DC 

voltage to control compressor 

speed. The inverter allows precise 

throttle control of the conditioning 

unit based on the load or need. 

Inverter units are quieter, more 

efficient and last longer. 

Ductless Mini-Split

 – An air 

conditioner or heat pump that 

requires no duct work to function. 

The unit hangs on the wall or 

ceiling and cools or heats the 

surrounding area. 

Evaporator

 – The indoor portion 

of the heat pump or air conditioner. 

In a mini-split system this hangs on 

the wall or ceiling and provides the 

heating or cooling of the space. 

H/P 

– Heat Pump. A unit that can 

operate as both an air conditioner 

or a heater. When it’s cold outside 

a heat pump extracts the outside 

heat and transfers it inside. When 

it’s warm outside, it reverses 

directions and acts like an air 

conditioner, removing heat. A 

heat pump moves heat instead 

of generating it, giving you more 

energy efficiency. 

HSPF

 – Heating Seasonal 

Performance Factor. The greater 

the number/rating the more 

efficient the heating. A 10 HSPF, 

for example is a very good rating.

Humidifier

 – Humidifiers use 

water to put humidity in the 

growing space. Many plants we 

grow indoors are accustomed 

to growing outdoors in tropical 

areas where humidity is high. Also 

certain parts of the country are 

drier than others so you will need 

to add humidity.

Line Set

 – Insulated copper tubing 

used to connect the evaporator 

and condenser. The refrigerant 

travels back and forth through the 

line set between the evaporator 

and condenser to create either 

cooling or heating. 

R-410

 – A type of refrigerant. 

Unlike alkyl halide refrigerants, 

R-410A (which contains only 

fluorine) does not contribute 

to ozone depletion. Because of 

that attribute it’s preferred and 

used more broadly instead of 

R-22 which are phased out. R-410 

refrigerants allow for higher SEER 

ratings therein reducing power 

consumption and improving unit 

efficiency. 

SEER

 – Seasonal Energy Efficiency 

Ratio. The greater the SEER rating, 

the more efficient the cooling 

system. The minimum SEER rating 

allowed by the Federal Government 

is 14. 

Ton

 – The size of air conditioning 

unit (heating or cooling) is 

common referred to in “tons”. A 

one ton unit, for example, is 12,000 

BTU’s. A two ton, 24,000 BTU’s, 

etc. This was arrived at using a 

standard of how long it would take 

to melt ice. A one ton unit takes 

12,000BTU’s of heat one hour to 

melt a ton of ice. 

VFD 

– Variable Frequency Drive. 

The VFD is a an electrical device 

that’s used to control the speed 

and torque of an air conditioning 

motor, like those used in an 

inverter compressor.

GLOSSARY OF TERMS

cr

NOTES

_______________________________________________________ 

_______________________________________________________

_______________________________________________________

_______________________________________________________

_______________________________________________________

_______________________________________________________

_______________________________________________________

_______________________________________________________

_______________________________________________________

Содержание 700807

Страница 1: ...ONER INSTALLATION MANUAL This manual only describes the installation of the indoor unit When installing the outdoor unit refer to the installation manual of outdoor unit 700807 700808 PRO MINI SPLIT I N D O O R W A L L M O U N T ...

Страница 2: ...our purchase of Ideal Air s Pro Mini Split indoor wall mount unit We re proud to offer this product and believe it s the very best in its class 2 SAFETY PRECAUTIONS 3 ACCESSORIES 5 INSTALLATION SUMMARY INDOOR UNIT 6 UNIT PARTS 8 INDOOR UNIT INSTALLATION 9 OUTDOOR UNIT INSTALLATION 17 REFRIGERANT PIPING CONNECTION 21 AIR EVACUATION 23 ELECTRICAL AND GAS LEAK CHECKS 25 TEST RUN 25 DISPOSAL GUIDELINE...

Страница 3: ...an cause water leakage electrical shock fire and can cause the unit to fail Install the unit in a firm location that can support the unit s weight If the chosen location cannot support the unit s weight or the installation is not done properly the unit may drop and cause serious injury and damage For all electrical work follow all local and national wiring standards regulations and the Installatio...

Страница 4: ...AUTION NOTE ABOUT FLUORINATED GASES This air conditioning unit contains fluorinated gases For specific information on the type of gas and the amount please refer to the relevant label on the unit itself Installation service maintenance and repair of this unit must be performed by a certified technician Product uninstallation and recycling must be performed by a certified technician If the system h...

Страница 5: ...and fire or equipment failure Name Shape Quantity 1 1 1 Clip anchor Mounting plate fixing screw ST3 9 X 25 Remote control Fixing screw for remote control holder ST2 9 x 10 Remote control holder Dry battery AAA LR03 Seal Drain joint Mounting plate 5 5 2 1 Optional Parts 2 1 1 User manual Installation manual Line sets sold separately Connecting pipe assembly Liquid side Gas side 6 35 1 4 9 52 3 8 9 ...

Страница 6: ...ation Page 9 And Drill Wall Hole Page 10 1 Attach Mounting Plate Page 10 2 Prepare Refrigerant Piping Page 12 4 3b 12cm 4 75 2 3m 90 55 12cm 4 75 15cm 5 9 Determine Wall Hole Position Page 10 3a INSTALLATION SUMMARY INDOOR UNIT ...

Страница 7: ...7 Mount Indoor Unit Page 16 STEP 8 Wrap Piping and Cable Page 15 1 2 3 Connect Drain Hose Page 13 Connect Signal Cable Page 14 5 6 7 8 ...

Страница 8: ...ont Panel Outdoor Unit Power Cable Some Units Remote Holder Remote Control Some Units UNIT PARTS NOTE ON ILLUSTRATIONS Illustrations in this manual are for explanatory purposes The actual shape of your indoor unit may be slightly different The actual shape shall prevail FIG 2 1 ...

Страница 9: ...rt the weight of the unit A location at least 1m 40 from all other electrical devices e g TV radio computer DO NOT INSTALL UNIT IN THE FOLLOWING LOCATIONS Near any source of heat steam or combustible gas Near flammable items such as curtains or clothing Near any obstacle that might block air circulation Near the doorway In a location subject to direct sunlight INSTALLATION INSTRUCTIONS INDOOR UNIT...

Страница 10: ...m 2 5 core drill drill a hole in the wall Make sure that the hole is drilled at a slight downward angle so that the outdoor end of the hole is lower than the indoor end by about 5mm 7mm 0 2 0 275 This will ensure proper water drainage See FIG 3 2 Place the protective wall cuff in the hole This protects the edges of the hole and will help seal it when you finish the installation process When drilli...

Страница 11: ...mm 1 55 Right rear wall hole 65mm 2 5 Model C 965mm 38 138mm 5 45 34mm 1 35 517 4mm 20 37 Indoor unit outline Left rear wall hole 65mm 2 5 219mm 8 6 553mm 21 77 300mm 11 8in 335mm 13 2 Right rear wall hole 65mm 2 5 Model D 1080mm 42 5 53 5mm 2 1 47mm 1 85 76mm 3 53 5mm 2 1 47mm 1 85 148 7mm 5 85 151mm 5 95 174 3mm 6 85 Indoor unit outline Left rear wall hole 65mm 2 5 172mm 6 8 362mm 14 25 Right re...

Страница 12: ...WILL AFFECT THE UNIT S PERFORMANCE Use scissors to cut down the length of the insulating sleeve to reveal about 15cm 6 of the refrigerant piping This serves two purposes a To facilitate the Refrigerant Piping Connection process b To facilitate gas leak checks and enable you to check for dents If existing connective piping is already embedded in the wall proceed directly to the Connect Drain Hose s...

Страница 13: ... a small amount of water into the drain pan to make sure that water flows from the unit smoothly PLUG THE UNUSED DRAIN HOLE To prevent unwanted leaks you must plug the unused drain hole with the rubber plug provided FIG 3 5 CORRECT Make sure there are no kinks or dent in drain hose to ensure proper drainage FIG 3 6 NOT CORRECT Kinks in the drain hose will create water traps FIG 3 7 NOT CORRECT Kin...

Страница 14: ...nit to an individual branch circuit outlet DO NOT connect another appliance to that outlet Make sure to properly ground the air conditioner Every wire must be firmly connected Loose wiring can cause the terminal to overheat resulting in product malfunction and possible fire DO NOT let wires touch or rest against refrigerant tubing the compressor or any moving parts within the unit STEP 6 CONNECT S...

Страница 15: ...the wire cover on the front of the unit and the plastic panel on the back STEP 7 WRAP PIPING AND CABLES Before passing the piping drain hose and the signal cable through the wall hole you must bundle them together to save space protect them and insulate them Bundle the drain hose refrigerant pipes and signal cable according to FIG 3 10 DRAIN HOSE MUST BE ON BOTTOM Make sure that the drain hose is ...

Страница 16: ...edded in the wall do the following Hook the top of the indoor unit on the upper hook of the mounting plate Use a bracket or wedge to prop up the unit giving you enough room to connect the refrigerant piping signal cable and drain hose Refer to FIG 3 11 for an example Connect drain hose and refrigerant piping refer to Refrigerant Piping Connection section of this manual for instructions Keep pipe c...

Страница 17: ...le to the direction of the wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See FIG 4 2 and FIG 4 3 above INSTALLATION INSTRUCTIONS OUTDOOR UNIT IF THE UNIT IS FREQUENTLY EXPOSED TO HEAVY RAIN OR SNOW Build a shelter above the unit it to protect it from the rain or snow Be careful not to obstruct air flow around the unit IF THE UNIT IS FREQUENTLY EXPOSED...

Страница 18: ...between their mounting feet Prepare the installation base of the unit according to the dimensions below FIG 4 4 WARNING W A B D Air inlet Air outlet Air inlet Outdoor Unit Dimensions mm in W x H x D Mounting Dimensions Distance A mm in Distance B mm in 681x434x285 26 8 x17 x11 2 460 18 10 292 11 49 700x550x270 27 5 x21 6 x10 62 450 17 7 260 10 24 780x540x250 30 7 x21 25 x9 85 549 21 6 276 10 85 84...

Страница 19: ...f 1 5 times the maximum current of the unit If connecting power to fixed wiring a switch or circuit breaker that disconnects all poles and has a contact separation of at least 3mm 125 must be incorporated in the fixed wiring The qualified technician must use an approved circuit breaker or switch Only connect the unit to an individual branch circuit outlet DO NOT connect another appliance to that o...

Страница 20: ... and place it to the side Match the wire colors labels with the labels on the terminal block and firmly screw the u lug of each wire to its corresponding terminal After checking to make sure every connection is secure loop the wires around to prevent rain water from flowing into the terminal Using the cable clamp fasten the cable to the unit Screw the cable clamp down tightly Insulate unused wires...

Страница 21: ... of 5m 16 5 Refer to the table below for specifications on the maximum length and drop height of piping MAXIMUM LENGTH AND DROP HEIGHT OF REFRIGERANT PIPING PER UNIT MODEL DO NOT DEFORM PIPE WHILE CUTTING Be extra careful not to damage dent or deform the pipe while cutting This will drastically reduce the heating efficiency of the unit STEP 2 REMOVE BURRS Burrs can affect the air tight seal of ref...

Страница 22: ... and even flaring STEP 4 CONNECT PIPES When connecting refrigerant pipes be careful not to use excessive torque or to deform the piping in any way You should first connect the low pressure pipe then the high pressure pipe MINIMUM BEND RADIUS When bending connective refrigerant piping the minimum bending radius is 10cm 4 See FIG 5 6 INSTRUCTIONS FOR CONNECTING PIPING TO INDOOR UNIT Align the center...

Страница 23: ...nts shown in the table above WARNING TORQUE REQUIREMENTS Outer Diameter of Pipe mm Tightening Torque N cm Add Tightening Torque N m Ø 6 35 Ø 0 25 1 500 11lb ft 1 600 11 8lb ft Ø 9 52 Ø 0 375 2 500 18 4lb ft 2 600 19 18lb ft Ø 12 7 Ø 0 5 3 500 25 8lb ft 3 600 26 55lb ft Ø 16 Ø 0 63 4 500 33 19lb ft 4 700 34 67lb ft Valve cover FIG 5 9 FIG 5 10 AIR EVACUATION PREPARATIONS AND PRECAUTIONS Air and for...

Страница 24: ...ing hexagonal wrench fully open both the high pressure and low pressure valves Tighten valve caps on all three valves service port high pressure low pressure by hand You may tighten it further using a torque wrench if needed OPEN VALVE STEMS GENTLY When opening valve stems turn the hexagonal wrench until it hits against the stopper DO NOT try to force the valve to open further WARNING NOTE ON ADDI...

Страница 25: ...L CODES AND MUST BE INSTALLED BY A LICENSED ELECTRICIAN GAS LEAK CHECKS There are two different methods to check for gas leaks SOAP AND WATER METHOD Using a soft brush apply soapy water or liquid detergent to all pipe connection points on the indoor unit and outdoor unit The presence of bubbles indicates a leak LEAK DETECTOR METHOD If using leak detector refer to the device s operation manual for ...

Страница 26: ...ient temperature is below 17 C In this instance you can use the MANUAL CONTROL button to test the COOL function Lift the front panel of the indoor unit and raise it until it clicks in place The MANUAL CONTROL button is located on the right hand side of the unit Press it 2 times to select the COOL function See FIG 8 1 Perform test run as normal This appliance contains refrigerant and other potentia...

Страница 27: ... greater the number rating the more efficient the heating A 10 HSPF for example is a very good rating Humidifier Humidifiers use water to put humidity in the growing space Many plants we grow indoors are accustomed to growing outdoors in tropical areas where humidity is high Also certain parts of the country are drier than others so you will need to add humidity Line Set Insulated copper tubing us...

Страница 28: ... answers to most common questions and a complete technical support library please visit www ideal air com All design and specifications herein are subject to change without notice for product improvement Contact Ideal AirTM for details updates and other information DO NOT return this product to the store where you purchased it ...

Отзывы: