176

87.6

10

22.2

22.2

43.2

INPUT 

-

OUTPUT 

-

OUTPUT 

+

INPUT 

+

TOP VIEW

176

SIDE VIEW

50

12

Model Name

Input Voltage Range (VDC)

Output Voltage (VDC)

Output Current (A) *

IDC-200A-12

9 - 18

12.5

16

IDC-200B-12

20 - 35

12.5

16

IDC-200C-12

30 - 60

12.5

16

IDC-200D-12

60 - 120

12.5

16

IDC-200A-24

9 - 18

24.5

8

IDC-200B-24

20 - 35

24.5

8

IDC-200C-24

30 - 60

24.5

8

IDC-200D-24

60 - 120

24.5

8

Model Name

Wire Size (up to 6 ft)

IDC-200A-12 / IDC-200A-24 

32V

30A

AWG # 6

IDC-200B-12 / IDC-200B-24 

32V

15A

AWG # 12

IDC-200C-12 / IDC-200C-24 

80V

10A

AWG # 14

IDC-200D-12 / IDC-200D-24 

125V

5A

AWG # 14

Model Name

Wire Size (up to 10 ft)

IDC-200A-12

32V

20A

AWG # 6

IDC-200B-12

32V

20A

AWG # 6

IDC-200C-12

32V

20A

AWG # 6

IDC-200D-12

32V

20A

AWG # 6

IDC-200A-24

32V

10A

AWG # 12

IDC-200B-24

32V

10A

AWG # 12

IDC-200C-24

32V

10A

AWG # 12

IDC-200D-24

32V

10A

AWG # 12

Safety & EMC

 - Emission

EN50081-1 / EN61000-6-3

 - Immunity

EN50082-1 / EN61000-6-1

 - Automotive

95/54/EC (IDC-200A & IDC-200B Series Only)

Input/ Output Connections

Quick Connect male 6.3mm / 1/4" flat blade

Dimensions (L x W x H)

176 x 88 x 50 mm / 6.9" x 3.5" x 1.9"

Weight

0.6 Kg / 1.4 lbs

*Note: Specifications are subject to change without notice

Fuse Specs

Fuse Specs

External Input Side Fuse & Wiring (Inline with "Input +" Terminal)

External Output Side Fuse & Wiring (Inline with "" Terminal)

Samlex America Inc 

110-17 Fawcett Road 

Coquitlam BC Canada V3K6V2 

1-800-561-5885 www.samlexamerica.com

IDC-200 SERIES SPECIFICATIONS

Input to output isolation

Output ripple & noise

Peak efficiency

Operating temperature

Humidity, non condensing        

Protections

Yes. > 400 V RMS

< 50 mV RMS

85%

-20

o

 to +30

o

 C,  (De-rate linearly to zero at 70

o

 C)

Max 95% 

Overload / short circuit on the output side; Over voltage on the output side;

Over voltage / transients on the input side; Reverse polarity on the input side; Over heating

* The output current indicated is the maximum current at the maximum input voltage