PRX-TSEC
tSec Multi-Technology Card Reader
Installation Manual | June 2017
23
7.18
Custom RS-485 Format
Applies to RS-485 programming mode only.
To set the custom RS-485 format select Y from the menu. You will be prompted to enter a format string. This
format string can be up to 64 characters. Press ESC to cancel your entry.
The format specifiers are all preceded by a % character.
This example shows a format configured to output the site code then a colon. This is followed by the card
number then a question mark. This is concluded with the Wiegand data in the currently configured Wiegand
format.
The example shown above will output something similar to:
00034463:00003242?6A987CB0C
Where:
00034463
is the site code of the card read
00003242
is the card number of the card read
6A987CB0C
is the raw Wiegand data of the card read in the currently configured Wiegand format.
The b specifier outputs in hexadecimal format. In all other cases uppercase means hexadecimal format and
lowercase means decimal format. The definitions of each specifier is listed in the table below:
Specifier
Definition
b
Raw Wiegand hexadecimal data
s or S
Decimal or hexadecimal site code
c or C
Decimal or hexadecimal card number
n
New line
e or E
Decimal or hexadecimal card serial number
p or P
Padded version of the decimal or hexadecimal card serial number. This is padded to
17 characters in decimal and 10 characters in hexadecimal.
%
Two % in a row will place a % in the output
7.19
Save and Restart
You must select the Save and Restart option to save your programming changes and restart the device by
pressing the S key. Failing to select this option and powering the unit down will result in a loss of your
programming changes.
In 125kHz programming mode, badge the programming card 12 times to restart the card reader.
i
The Restart function immediately causes the card reader to exit programming mode and restart.