PROTECTIONS
Overload Protection:
The Inverter will shut down if the AC output is shorted, or if the
continuous draw exceeds 300 Watts for more than three seconds. The Inverter can be
manually reset by turning the Power Switch located on the front panel off, then on. The
Inverter can supply up to 600 Watts during the overload event, allowing this inverter to start
larger loads.
Under Voltage Protection:
The Inverter will shut down if the battery discharges below 10.5
Vdc (21.0 Vdc for 24V Inverter / 42.0 Vdc for 48V Inverter). The Inverter will automatically
restart when battery voltage rises to at least 11.8 Vdc (23.6 Vdc for 24V Inverter / 47.2 Vdc for
48V Inverter).
Over Voltage Protection:
The Inverter will shut down if the battery voltage exceeds 16.0 Vdc
(32.0 Vdc for 24V Inverter / 64.0 Vdc for 48V Inverter). The Inverter will automatically restart
when battery voltage drops below 15.0 Vdc (30.0 Vdc for 24V Inverter / 60.0 Vdc for 48V
Inverter).
Over Temperature Protection:
If the Inverter is subjected to higher ambient temperatures
than than the maximum rated temperature, or if the cooling vents or fan openings are blocked,
the unit will shut down. The Inverter will automatically restart after the unit cools down.
3
Figure 1: ICT Inverter Front Panel
Figure 2: ICT Inverter Back Panel
POWER SWITCH
AC STATUS LED
(GREEN)
FAULT LED
(RED)
COOLING FAN (TEMPERATURE CONTROLLED)
AC OUTLETS
GROUND CONNECTOR
NEGATIVE DC INPUT
POSITIVE DC INPUT