Output Current Influence on Output Load Operation
The table below helps illustrate how the total output current drawn from the power supply module influences
the operation of V1 and V2 outputs.
Output Load Current
Output Load Operation Status
0 - 8.0A
8.0-8.2A
8.2A - Short Circuit
Outputs Enabled (Mains Power)
Outputs Supplied by Battery
Output Over-Current Failure Trouble Input Activated
Over-Current Output Shutdown Activated
Core Temperature on Output Load Operation
The table below helps illustrate how the core temperature of the power supply module influences the operation
of the V1 and V2 outputs.
Core Temperature
Output Load Operation Status
<70°C
70-80°C
>80°C
Outputs Enabled (Mains Power)
Outputs Supplied by Battery
Output Over-Current Failure Trouble Input Activated
Over-Current Output Shutdown Activated
PRT-PSU-DIN-8A | Protege DIN Rail 8A Intelligent Power Supply | Installation Manual