Addressing the Touchscreen
The touchscreen comes online in Protege GX as an
analog expander
. By default it has an address of 254, which is
outside the range that the controller will accept. You will need to change this to bring the touchscreen online.
To set the address on the touchscreen:
1.
Power cycle the unit.
2.
Open the
Settings
page.
3.
The
Address
will be editable for 2 minutes. Use the
+/-
buttons to set the required address.
Trouble Inputs
Each touchscreen can monitor up to 8 trouble inputs.
Trouble inputs are used to monitor the module status and in most cases are not physically connected to an
external input.
The following table details the trouble inputs that are configured in the system and the trouble groups that they
are associated with.
Trouble Input
Function
Default
Trouble
Group
Default Trouble
Group Option
AEXXX:01
Module Tamper
Opens when the touchscreen is removed from the
wall.
System
Module Tamper
AEXXX:02 - 07
Reserved
-
-
AEXXX:08
Module Offline
The touchscreen has either been removed from the
system or lost communications.
System
Module Lost
Replace 'xxx' with the appropriate address of the module that you are programming.
Error Messages
Error messages are displayed beneath the On/Off button on the touchscreen.
⦁
Network status offline
: The touchscreen has no connection to the control unit. Check the address and
programming.
⦁
Locked out
: The room controller system has been disabled by the building manager. Contact the building
manager.
⦁
Leak detected
: A leak has been detected in the air conditioning unit. Contact the service company.
⦁
Balcony door left open
: An external door has been left open. The air conditioner will be deactivated
automatically (see page 12).
PRT-TS50-TH | Protege 5" Touchscreen | Installation Manual