4. Install fuse on the front of the panel for each output terminal block. The fuse number on the front
of the panel matches the output terminal block number on the back of the panel. Consult your local
electrical codes for wire ampacity and fuse sizing. Typically, fuses and wiring are derated to 80% of
their rating (e.g. 12 Amps maximum for a 15 Amp fuse).
5. Remove the plastic caps covering the input insulated studs.
For
the
ICT180-12BRC
(Positive Ground):
Connect the RTN (+) of the power source to the RTN insulated stud and the BAT (-) of the
power source to the BAT insulated stud.
For
the
ICT180-12BRCP
(Negative Ground):
Connect the positive of the power source to the positive insulated stud (labeled “+”) and the
negative of the power source to the negative insulated stud (labeled “-”).
6. Re-install plastic shield(s) to the output terminal block(s) and plastic caps to the input studs.
7. For remote monitoring and power control, connect your network interface to the Ethernet port on
the back of the panel. The recommended cable for Ethernet connection is Cat5e UTP network cable.
8. The Alarm Form “C” Contacts on the back of the panel can be connected to an external alarm circuit
to monitor alarms generated by the panel. Depending on the alarm circuit (refer to table 2), connect it
between normally open (NO) and common (C), between normally close (NC) and common (C), or both.
The built-in web server controls this alarm. The alarm connector can be unplugged from the panel for
easy installation.
9. For monitoring external Dry Contact sensors, connect each sensor between an Alarm Input (1 - 5)
and common (C) on the alarm input connector. The alarm input connector can be unplugged from the
panel for easy installation. Refer to table 3 for the alarm input connector pin-out.
10. Power up the distribution panel, and check for proper operation of the connected load(s), fuse
status LEDs, LCD, form “C” alarm (if using) and Ethernet communications (if connected).
5
LED
FUSE STATUS
ON
Blown
OFF
Good
Table 1: Fuse Status LED