Trip Amplifier EGS80X002001
Editing Device Data: Current Output
6.5.2 Fault Current
The following table shows the current output in the event of a fault, depending on the characteristic.
6.5.3 Start Value and End Value
Please note when entering
Start value
and
End value
:
• Both values are to be entered in the units, which were selected under
Units
• Values between 0 mA and 20 mA can be entered, or between the values of these limits converted
into the selected units, using the parameters
Zero point
and
Conversion factor
The difference between
End value
and
Start value
must be at least 1 % of the
End value
(preset automatically by the device).
Setting
0 mA to 20 mA
4 mA to 20 mA NE43
4 mA to 20 mA
Up/Down
21.5 mA
21.5 mA
22 mA
with short-circuit
with short-circuit
with short-circuit
(not distinguishable from
End value
overrange)
0 mA
2.0 mA
0 mA
with lead breakage
with lead breakage
with lead breakage
(not distinguishable from
Start value
measurement)
(not distinguishable from
Start value
underrange)
Hold
Last measured value before the fault
Max
21.5 mA
21.5 mA
22 mA
(not distinguishable from
End value
overrange)
Min
0 mA
2.0 mA
0 mA
(not distinguishable from
Start value
measurement)
(not distinguishable from
Start value
underrange)
Содержание WIKA EGS80
Страница 1: ...Operating instructions EN Digital limit switch model EGS80 Digital limit switch model EGS80...
Страница 37: ...70101419 2018 12 35 Trip Amplifier EGS80X002001 Notes...
Страница 38: ...70101419 2018 12 36 Trip Amplifier EGS80X002001 Notes...
Страница 39: ...70101419 2018 12 37 Trip Amplifier EGS80X002001 Notes...
Страница 40: ......