4 Modbus TCP/RTU Interface
The GW-7433D supports class 0, class 1 and partial class 2 Modbus slave
functionalities. The Modbus TCP client or Modbus RTU master connected to
the GW-7433D needs to follow the Modbus TCP/RTU specification 1.0.
The GW-7433D can handle maximum 5 Modbus TCP connections, and one
RS-232(COM1) or RS-485(COM2) connection simultaneously.
4.1 Commands
The following Modbus TCP/RTU commands are supported by the GW-7433D.
Function
Function Name
Class
Affects
Data Type
1
Read Multiple Coils
1
DO
Bit
2
Read Multiple Input Discrete
1
DI
Bit
3
Read Multiple Registers
0
AO
Word
4
Read Multiple Input Registers
1
AI
Word
5
Write Single Coil
1
DO
Bit
6
Write Single Register
1
AO
Word
15
Force Multiple Coils
2
DO
Bit
16
Force Multiple Registers
0
AO
Word
Table 4-1: Modbus Commands
GW-7433D MODBUS TCP/RTU to CANopen Gateway User Manual
25
(Version 2.1.0, Aug/2019)