background image

8

4  MAINTENANCE

3.4 

AIRFLOW VERIFICATION

Verify  the  airflow  by  taking  readings  of  the  following  points, 
while the elements are in the heating mode: 

WARNING

x

 

Total amperage of all the heating elements; 

Electrical shock hazard. 

x

 

Voltage at the furnace; 

Turn  OFF  power  to  the  furnace  before  any  disassembly  or 
servicing. 

x

 

Supply air temperature.  The point of the reading must 
not be affected by radiant heat from the elements; 

Failure  to  do  so  can  result  in  death,  bodily  injury  and/or 
property damage.

x

 

Return air temperature. 

From  these  readings,  one  can  arrive  at  an  approximate 
calculation  of  the  average  airflow.    To  do  that,  the  following 
formulae should be used: 

Preventive  maintenance  is  the  best  way  to  avoid  unnecessary 
expense  and  inconvenience.    Have  your  heating  system 
inspected  by  a  qualified  service  technician  at  regular  intervals.  
Do  not  attempt  to  repair  the  furnace  or  its  controls.    Call  a 
qualified service technician. 

 

 

0.82 x amps. x volts 

Liter/s=  ------------------------- 
 

 

Diff. temperature ˚C

 

 

3.1 x amps. x volts 

Before calling for repair service, check the following points: 

CFM =  ------------------------ 

1)  Check fuses or the circuit breaker; 

 

 

Diff. temperature ˚F

2)  Check  if  the  15  A  circuit  breaker  on  the  furnace  is 

disengaged; 

3.4.1.

Supply Air Temperature Rise Test

3)  Set  the  thermostat  higher  than  room  temperature.    If 

the  unit  does  not  start  up,  cut  the  power  and  call  la 
qualified service technician. 

1)  Operate  the  unit  at  maximum  power  for  at  least  10 

minutes;

2)  Measure the air temperature in the return air plenum; 

When calling for service or ordering a replacement part, specify 
the model and serial number of your appliance. 

3)  Measuring  the  air  temperature  in  the  largest  trunk 

coming  off  the  supply  air  plenum,  just  outside  the 
range of radiant heat from the heat exchanger.  0.3 m 
(12”)  from  the  plenum  of  the  main  take-off  is  usually 
sufficient;

4.1 

AIR FILTER

The  filter  supplied  with  the  unit  is  the  disposable  type  and 
should be replaced twice a year.  The presence of animal hair, 
dust, etc. may  necessitate more frequent changes.  Dirty filters 
have  an  adverse  effect  on  the  performance  of  the  central 
heating system. 

4)  The  temperature  rise  is  calculated  by  subtracting  the 

return air temperature from the supply air temperature. 

If  the  temperature  rise  exceeds  the  temperature  specified  in 
Table 1, p.10, change to the next higher blower speed tap, until 
the temperature rise falls to the target or below.  If the excessive 
temperature  rise  cannot  be  reduced  by  increasing  fan  speed, 
investigate  for  ductwork  obstructions  or  dirty  and  improper  air 
filter.

4.2 

MOTOR LUBRICATION

Do  not  lubricate  the  blower  motor,  since  it  is  permanently 
lubricated. 

CAUTION 

It is important to check the airflow and to ascertain that the unit 
does  not  operate  above  the  temperatures  specified  in  the 
Technical Specifications (Table 1).  This is particularly important 
if a cooling coil or a heat pump has been installed in the ducts. 

Hi-Limit thermal protectors should never need to engage during 
the  normal  functioning  of  the  appliance.    They  are  strictly 
designed  to  engage  during  the  improper  functioning  of  the 
blower or when the filter was improperly maintained. 

3.4.2.

Vérification des limiteurs de température

After  operating  the  furnace  for  at  least  15  minutes,  restrict  the 
return air supply  by blocking  the filters  or the return air register 
and  allow  the  furnace  to  shut  off  on  High  Limit.    The  electric 
heaters  must  deactivate  themselves  one  by  one  before  the 
warm air temperature exceeds 200˚F

Remove the obstruction and the elements should restart after a 
few minutes. 

Содержание SUPREME FEM10-M2401AM-A

Страница 1: ...ebec Canada J1L 1V8 Caution Do not tamper with the unit or its controls Call a qualified service technician Printed in Canada Printed on 100 recycled paper DNS 0981 Rev A MULTI POSITION INSTALLER SERV...

Страница 2: ...ON 8 5 INFORMATION 9 TABLES AND FIGURES FIGURE 1 CONFIGURATION UPFLOW INSTALLATION 4 FIGURE 2 CONFIGURATION DOWNFLOW INSTALLATION 4 FIGURE 3 CONFIGURATION HORIZONTAL INSTALLATION 4 FIGURE 4 MANUAL FUR...

Страница 3: ...ualified persons can result in hazards to them and to others Installations must conform to local codes or in the absence of same to codes of the country having jurisdiction The information contained i...

Страница 4: ...uding 20 k W can be installed with a zero clearance to combustible material Ducts for furnaces of 23 kW or more must have a clearance of 25 mm 1 to combustible material for the first 0 9 m 36 of duct...

Страница 5: ...ontrol the temperature of the area to be heated Follow the instructions supplied with the thermostat Install the thermostat on an interior wall in a location where it will not be subject to direct sun...

Страница 6: ...airflow refer to the following table as well as the airflow tables based on static pressure in the Technical Specifications section of this manual For the adjustment of the airflow on heating mode to...

Страница 7: ...t of the room is in the heating mode and is set higher than the ambient temperature To start the unit turn the main electrical switch on 3 2 OPERATING SEQUENCE Heating mode 1 The thermostat closes the...

Страница 8: ...pply air plenum just outside the range of radiant heat from the heat exchanger 0 3 m 12 from the plenum of the main take off is usually sufficient 4 1 AIR FILTER The filter supplied with the unit is t...

Страница 9: ...ame and address START UP RESULTS Voltage Total current consumed by the elements Supply air temperature Return air temperature Supply air duct static pressure Return air duct static pressure Total pres...

Страница 10: ...84 100 112 125 119 134 155 Maximum size circuit breaker Amp 2 60 90 100 125 125 125 150 175 BLOWER DATA factory adjusted to a static pressure of 0 5 W C Blower speed at 0 50 W C static pressure LOW M...

Страница 11: ...5 CFM more or less These readings were taken with the air filter installed TABLE 3 Air Flow CFM SUPREME with 1 HP motor 0 1 0 2 0 3 0 4 0 5 0 6 0 7 LOW 1035 1030 1030 1025 1020 1020 1015 MED LOW 1315...

Страница 12: ...12 FIGURE 6 Wiring Diagram 10 kW with 1 3 HP motor...

Страница 13: ...13 FIGURE 7 Wiring Diagram 15 kW with 1 3 HP motor...

Страница 14: ...14 FIGURE 8 Wiring Diagram 18 and 20 kW with 1 3 HP motor and 20 kW with 1 0 HP...

Страница 15: ...15 FIGURE 9 Wiring Diagram 23 kW with 1 3 HP and 1 HP motor...

Страница 16: ...16 FIGURE 10 Wiring Diagram 27 kW with 1 HP motor...

Страница 17: ...COMPONENTS AND REMPLACEMENT PARTS 17...

Страница 18: ...18 PARTS LIST Exploded View B50002F Please refer to Table 4 p 20...

Страница 19: ...HP 12 B03288 MOUNTING PLATE FOR ELECTRICAL TOP 13 B03289 MOUNTING PLATE FOR ELECTRICAL SIDE 14 L05F004 TERMINAL STRIP 4 POSITION 15 L01H009 RELAY SPDT 24 VAC 16 L01F009 TRANSFORMER 120 24Volts 17 L99...

Страница 20: ...7 305891 R02N016 305891 R02N016 305136 R02N017 305136 R02N017 18C 3 305136 R02N017 305891 R02N016 305891 R02N016 305891 R02N016 18D 4 305891 R02N016 305136 R02N017 18E 5 305891 R02N016 Item TABLE 4 FE...

Отзывы: