background image

Содержание PA55 Series

Страница 1: ...Heater Wiring 6 Grounding 6 Installing Wrong 6 Unit Disconnect Breaker 8 Rain Shield Installation 8 6 Air Distribution System 8 Ductwork 8 DuctworkInsulation 8 DactwerkConnections 8 Filters 8 7 Start...

Страница 2: ...lso work The slab or blocks SHOULD NOT be in contact with any part of the structure Check local codes covering zoning noise platforms etc If practical avoid locating next to fresh air intakes vent or...

Страница 3: ...is to the outside 2 Make sure when pushing the collars into place that the V flange of the collars seats into the supply and return holes securely 3 Re install screw in each collar so it goes through...

Страница 4: ...ctric heat mounting plate for the ground connection Use a copper conduc tor of the appropriate size from the unit to a grounded connection in the electrical service panel or to a properly driven and e...

Страница 5: ...cturer s instruc tions for the devices FIGURE 5 I HarnessElectr niCconnectionTherm statDiagramL W Voltage Wi ring Typical Thermostat Subbase c R _ _ I I I I I I I I I I _ _ _ _ when used I I I I i i i...

Страница 6: ...mplify wir ing of heaters 3 From inside the blower compartment remove the six screws on the heater cover plate and save the screws Discard the heater cover plate The screws will be used later to mount...

Страница 7: ...thermostat at the field supplied low volt wire harness in the control box 8 Connect the grey wire from the heater wire harness to the blue wire from the unit 24V common Unit Line Voltage Wires Knockou...

Страница 8: ...sizing and installation to Mobile Homes and other standard construction Ductwork Insulation It is recommended that ductwork installed outdoors have a mini mum of 2 51 mm of fiberglass insulation and b...

Страница 9: ...product are based on a nominal 400 CFM per ton cooling and the basic mid range on the temperature rise for heating Since the manufacturer cannot establish the static pressure that will be applied to t...

Страница 10: ...efer to the unit s Installation Instructions for airflow information A temperature rise greater than 60 F 33 3 C is not recom mended This applies to electric heat only 1 To check the temperature rise...

Страница 11: ...ld detergent and rinsing with cold water Replace filters with the arrows on the side pointing in the direction of air flow Dirty filters are the most com mon cause of inadequate heating or cooling per...

Страница 12: ...lint Clean the compartment and the blower wheel If accu mulation is excessive on blower wheel or does not easily remove it may be necessary to remove and disassemble the blower assembly for proper cle...

Страница 13: ...Warranty DOES NOT COVER any labor material refractory chambers oii nozzles refrigerant refrigerant inspection and refrigerant reclaiming freight and or handling charges associated with any repair or r...

Страница 14: ...CAC4 KAC0 TCA0 TCA2 TCA4 HHP0 HHP2 HHP4 CliP0 CliP2 CliP4 TCH0 TCH2 TCH4 PGME PYMC PHAD PGAD PA95 PAPC PAK APK Tothe original purchaser a replacement for 10 years from original date of installation o...

Отзывы: