ICP N9MSB Скачать руководство пользователя страница 28

SERVICE AND TECHNICAL SUPPORT MANUAL

Gas Furnace: N9MSB

Specifications  subject to change without notice.

28

440 04 4413 03

SEQUENCE OF OPERATION

NOTE

:  Furnace control must be grounded for proper operation

or control will lock out. Control is grounded through

green/yellow wire routed to gas valve and manifold bracket

screw. Using the schematic diagram in 

Figure 15

, follow the

sequence of operation through the different modes. Read and

follow the wiring diagram very carefully.

NOTE

:  If a power interruption occurs during a call for heat (W),

the control will start a 90

second blower

only ON period two

seconds after power is restored, if the thermostat is still calling

for gas heating. The GREEN LED light will flash code 1+2

during the 90

second period, after which the LED will be

flashing a heartbeat, as long as no faults are detected. After the

90

second period, the furnace will respond to the thermostat

normally.

The blower door must be installed for power to be conducted

through the blower door interlock switch ILK to the furnace

control CPU, transformer TRAN, inducer motor IDM, blower

motor BLWM, hot

surface igniter HSI, and gas valve GV.

1.

Heating

 

The wall thermostat “calls for heat,” closing the R

to

W

circuit. The furnace control performs a self

check,

verifies the pressure switch contacts collector box

LPS

and housing pressure

HPS are open, and starts the

inducer motor IDM.
a.

Inducer Prepurge Period

 As the inducer motor IDM

comes up to speed the collector box pressure switch

contacts LPS close to begin a 15 second prepurge

period. The inducer housing pressure switch contacts

HPS are ignored until one minute after the gas valve

closes.

b.

Igniter Warm

Up

 At the end of the prepurge period,

the Hot

Surface igniter HSI is energized for a

17

second igniter warm

up period.

c.

Trial

for

Ignition  Sequence

 When the igniter

warm

up period is completed, the main gas valve relay

contacts GVR close to energize the gas valve GV, the

gas valve opens, and 24 vac power is supplied for a

field

installed humidifier at the HUM 24VAC terminal.

The gas valve GV permits gas flow to the burners where

it is ignited by the HSI. Five seconds after the GVR

closes, a 2

second flame proving period begins. The

HSI igniter will remain energized until the flame is

sensed or until the 2

second flame proving period

begins.

d.

Flame

Proving

 When the burner flame is proved at

the flame

proving sensor electrode FSE, the furnace

control CPU begins the blower

ON delay period and

continues to hold the gas valve GV open. If the burner

flame is not proved within two seconds, the control CPU

will close the gas valve GV, and the control CPU will

repeat the ignition sequence for up to three more

Trials

For

Ignition  before going to Ignition

Lockout.

Lockout will be reset automatically after three hours or

by momentarily interrupting 115 vac power to the

furnace, or by interrupting 24 vac power at 24VAC or

COM to the furnace control CPU (not at W, G, R, etc.).

If flame is proved when flame should not be present, the

furnace control CPU will lock out of Gas

Heating mode

and operate the inducer motor IDM until flame is no

longer proved.

e.

Blower

On Delay

 If the burner flame is proven, the

blower motor is energized on HEAT speed 25 seconds

after the gas valve GV is energized. 

Simultaneously, the electronic air cleaner terminal EAC

is energized and remains energized as long as the

blower motor BLWM is energized.

f.

Heat

Off Delay

 When the thermostat is satisfied, the

R

to

W circuit is opened, de

energizing the gas valve

GV, stopping gas flow to the burners, and de

energizing

the humidifier terminal HUM 24 VAC. The inducer motor

IDM will remain energized for a 15

second post

purge

period. The blower motor BLWM and air cleaner terminal

EAC will remain energized for 90, 120, 150, or 180

seconds (depending on the heat

OFF delay selection).

The furnace control CPU is factory

set for a

120

second heat

OFF delay.

2.

Cooling Mode

The thermostat “calls for cooling.”

The thermostat closes the R

to

G

and

Y circuits. The R

to

Y

circuit starts the outdoor unit, and the furnace control

R

to

G

and

Y circuits start the furnace blower motor BLWM

on COOL speed. 

The electronic air cleaner terminal EAC is energized with 115

vac when the blower motor BLWM is operating. When the

thermostat is satisfied, R

to

G

and

Y circuits are opened. The

outdoor unit will stop, and the furnace blower motor BLWM will

continue operating on the COOL speed for an additional 90

seconds. (See 

Figure 4

) Jumper J2 can be cut to reduce the

cooling

OFF delay to 5 seconds. (See 

Figure 4

)

3.

Continuous Blower Mode 

When the R

to

G circuit is closed by the thermostat, the

blower motor BLWM will operate on heat speed and EAC

terminal is energized as long as the blower motor BLWM

is energized. During a call for heat, the blower BLWM will

stop during igniter warm

up (17 seconds), ignition (7

seconds), and blower

on delay (25 seconds), allowing

the furnace heat exchangers to heat up more quickly,

then restarts at the end of the blower

on delay period at

HEAT speed. 

In heating, the furnace control CPU will continue running

the blower motor BLWM at HEAT speed after the

selected blower

OFF delay period is completed.

When the thermostat “calls for cooling”, the blower motor

BLWM will operate at COOL speed. When the thermostat

is satisfied, the blower motor BLWM will operate an

additional 90 seconds on COOL speed before reverting

back to continuous

blower speed. 

When the R

to

G circuit is opened, the blower motor

BLWM will continue operating for an additional 5

seconds, if no other function requires blower motor

BLWM operation.

4.

Heat Pump Mode

Change Heat Pump to: HEAT PUMP MODE. When

installed with a heat pump, the furnace control

automatically changes the timing sequence to avoid long

blower off times during demand defrost cycles. When the

R-to-W-and-Y  or R-to-W-and-Y-and-G circuits are

energized the furnace control CPU will continue to turn

on the blower motor BLWM at HEAT speed, and begin a

heating cycle. The blower motor BLWM will remain on

until the end of the prepurge period, then shut off for 24

seconds then come back on at HEAT speed. When the

W input signal disappears, the furnace control begins a

normal inducer post-purge period and the blower

switches to COOL speed after a 3 second delay. If the

R-to-W-and-Y-and-G signals disappear at the same time,

the blower motor BLWM will remain on for the selected

blower-OFF delay period. If the R-to-W-and-Y signals

disappear, leaving the G signal, the blower motor BLWM

will continue running the blower motor BLWM at HEAT

speed after the selected blower-OFF delay period is

completed.

See Component Self Test

Refer to page 16 for instructions.

Содержание N9MSB

Страница 1: ...ls The signal word WARNING is used throughout this manual in the following manner Safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury TABLE OF CONTENTS START UP CHECK SHEET FOR PSC MOTOR 3 START UP ADJUSTMENT AND SAFETY CHECK 4 PRIME CONDENSATE TRAP WITH WATER 4 PURGE GAS LINES 4 ADJUST TEMPERATURE RISE 10 ADJUST BLO...

Страница 2: ...death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation WARNING PERSONAL INJURY AND OR PROPERTY DAMAGE HAZARD Failure to carefully read and follow this w...

Страница 3: ...eam of Furnace Drip Leg Gas Valve turned ON Type of Gas Natural Propane Filter Type and Size Check in box the Blower OFF Delay Jumper Heating Position for Fan Time OFF Setting 1 and 2 2 and 3 3 and 4 5 and 6 90 120 150 180 Calculated Input BTU Rate See Checks and Adjustments Section Heating Check Measured Line Pressure During Heat Measured Manifold Pressure Heat Temperature of Supply Air Heat Temp...

Страница 4: ...ON Before operating furnace check flame rollout manual reset switch for continuity If necessary press button to reset switch EAC 115vac terminal is energized whenever blower operates HUM 24vac terminal is only energized the draft inducer is energized in heating Prime Condensate Trap with Water CARBON MONOXIDE POISONING HAZARD Failure to follow these warnings could result in personal injury or deat...

Страница 5: ... gas heating values Refer to the instructions provided in the factory specified Propane conversion kit for instructions for setting gas manifold pressures for Propane applications In the USA the input rating for altitudes above 2000 ft 610 M must be reduced by 2 percent for each 1000 ft 305 M above sea level refer to Table 1 The natural gas manifold pressures in Table 3 adjust for BOTH altitude an...

Страница 6: ...ometer to the inlet pressure tap on gas valve 4 Turn on furnace power supply 5 Turn gas supply manual shutoff valve to ON position 6 Turn furnace gas valve switch to ON position 7 Jumper R and W thermostat connections at the furnace control board 8 When main burners ignite confirm inlet gas pressure is between 4 5 in w c 1125 Pa and 13 6 in w c 3388 Pa 9 Remove jumper across thermostat connections...

Страница 7: ...lution and note reading The 2 or 5 cubic feet dial provides a more accurate measurement of gas flow e Refer to Table 2 for cubic ft of gas per hr f Multiply gas rate cu ft hr by heating value Btuh cu ft to obtain input If clocked rate does not match required input from Step 1 increase manifold pressure to increase input or decrease manifold pressure to decrease input Repeat steps b through e until...

Страница 8: ...FORMER 24 VAC CONNECTIONS P2 HOT SURFACE IGNITOR HSI INDUCER MOTOR IND CONNECTOR 115 VAC L1 LINE VOLTAGE CONNECTION SPARE1 COM BLUE 115 VAC L2 NEUTRAL CONNECTIONS 24 V THERMOSTAT TERMINALS HUMIDIFIER TERMINAL 24 VAC 0 5 AMP MAX 3 AMP FUSE LED OPERATION DIAGNOSTIC LIGHT 24VAC RED BLOWER SPEED SELECTION TERMINALS HUM XFMR HUMIDIFIER TERMINAL 115 VAC 120 180 90 150 SPARE2 J2 JUMPER J2 HUM 24VAC BLW S...

Страница 9: ... 300 21 171 343 857 62 58 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 237 29 124 248 621 78 46 92 231 30 120 240 600 80 45 90 225 31 116 232 581 82 44 88 220 32 113 225 563 84 43 86 214 33 109 218 545 86 42 84 209 34 106 212 529 88 41 82 2...

Страница 10: ...3 42 3 4 42 3 5 42 3 6 3001 800 43 3 8 42 3 2 42 3 3 42 3 4 915 825 43 3 6 43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219 925 44 3 2 44 3 4 44 3 5 44 3 6 950 44 3 1 44 3 2 44 3 3 44 3 4 750 42 3 3 42 3 4 42 3 5 42 3 6 4001 775 43 3 7 43 3 8 42 3 3 42 3 4 1220 800 43 3 5 43 3 6 43 3 7 43 3 8 825 44 3 8 43 3 4 43 3 5 43 ...

Страница 11: ...ading Leaving blower door off will result in incorrect temperature measurements due to possible changes in duct static pressure and airflow FURNACE DAMAGE HAZARD Failure to follow this caution may result in S Overheating the heat exchangers or condensing flue gases in heat exchanger areas not designed for condensate S Shortened furnace life S Component damage Temperature rise must be within limits...

Страница 12: ...se terminals R and W The thermostat anticipator should NOT be in the circuit while measuring current 1 Remove thermostat from sub base or from wall 2 Connect an amp meter across the R and W sub base terminals or R and W wires at wall 3 Record amp draw across terminals when furnace is in low heat and after blower starts 4 Set heat anticipator on thermostat per thermostat instructions and install on...

Страница 13: ... Verify that there are no unsealed openings in the blower shelf or casing 5 Verify that the blower lower door in upflow position and control Main or upper door in upflow position doors are properly installed 6 Verify that the Status LED heartbeat bright dim If not check that the power supply is energized and that the blower door is secure See Figure 14 to interpret diagnostic codes 7 Cycle test fu...

Страница 14: ...1665 1640 1595 1545 1485 1410 1330 1235 1135 Orange 3 5 397 1485 1470 1455 1430 1390 1340 1280 1205 1120 1035 Blue 3 2 5 426 1120 1110 1100 1090 1065 1035 990 935 870 805 Red 3 2 0 433 940 920 910 890 865 830 790 745 690 625 1002116 SIDE BOTTOM Black 4 0 373 1715 1660 1610 1555 1490 1420 1340 1245 1150 1065 Yellow 3 3 5 379 1535 1480 1435 1380 1325 1260 1180 1095 1010 910 Blue 3 3 0 367 1300 1255 ...

Страница 15: ...blower is located below the combustion and controls section of the furnace and conditioned air is discharged upward Since this furnace can be installed in any of the 4 positions shown in Figure 6 you must revise your orientation to component location accordingly Figure 6 Multipoise Orientations A93041 Electrical Controls and Wiring Pressure Switches Each pressure switch is labeled with the referen...

Страница 16: ... are active The stored status codes will NOT be erased from the control memory when 115 or 24 V power is interrupted See the Service Label See Figure 14 for more information The most recent fault code may be retrieved as follows 1 Leave 115 V power connected to furnace 2 Observe the status LED through the blower door the lower door on upflow applications indicator Refer to the Service Label See Fi...

Страница 17: ...ace with filter or filtration device access doors removed WARNING CUT HAZARD Failure to follow this caution may result in personal injury Sheet metal parts may have sharp edges or burrs Use care and wear appropriate protective clothing safety glasses and gloves when handling parts and servicing furnaces CAUTION The minimum maintenance on this furnace is as follows 1 Check and clean air filter each...

Страница 18: ...teps a through e g Tighten all clamps 15 lb in See Figure 8 for steps 5 through 14 5 Remove screws securing blower assembly to blower shelf and slide blower assembly out of furnace Detach ground wire and disconnect blower motor harness plugs from blower motor NOTE Blower wheel is fragile Use care 6 Clean blower wheel and motor by using a vacuum with soft brush attachment Be careful not to disturb ...

Страница 19: ...supply and cycle furnace through one complete heating cycle Verify the furnace temperature rise as shown in Adjustments Section Adjust temperature rise as shown in Adjustments Section Cleaning Burners and Flame Sensor The following items must be performed by a qualified service technician If the burners develop an accumulation of light dirt or dust they may be cleaned by using the following proced...

Страница 20: ... Figure 10 and Figure 11 Figure 10 Igniter Position Top View A11405 2 1 2 in 64 4 1 1 4 in 31 8 Figure 11 Igniter Position Side View L12F041 2ïin 2 5 mm 3 8ïin 3 16ïin 0 8 ï1 5 mm 50 mm 9 6 mm 4 6 mm 1 10ïin 1 32 ï 1 16ïin 9 Attach the wires to the roll out switches 10 Align the burner assembly with the openings in the primary cell inlet panel and attach the burner assembly to the cell panel 11 Co...

Страница 21: ...rt on collect box and the trap with a small wire Shake any water out of the tube 13 Reconnect relief tube to trap and collector box ports Cleaning Condensate Drain and Trap NOTE If the condensate trap is removed a new gasket between the trap and collector box is required Verify a condensate trap gasket is included in the service kit or obtain one from your local distributor 1 Disconnect power at e...

Страница 22: ...y restrict flow of combustion products 8 Reverse items 6 through 1 for reassembly 9 Refer to furnace wiring diagram and reconnect wires to flame rollout switch gas valve igniter and flame sensor 10 Turn on gas and electrical supplies to furnace 11 Check furnace operation through two complete heat operating cycles Look at burners Burner flames should be clear blue almost transparent See Figure 13 F...

Страница 23: ...the funnel tube Antifreeze should run through the collector box overfill condensate trap and flow to an open drain 8 Replace the rubber plug in the port on the collector box 9 Remove the middle unused rubber plug from the port on the collector box opposite the condensate trap See Figure 1 10 Repeat Steps 5 through 8 11 If a condensate pump is used check with pump manufacturer to verify pump is saf...

Страница 24: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace N9MSB Specifications subject to change without notice 24 440 04 4413 03 Figure 14 Service Label 338310 2 Rev F ...

Страница 25: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace N9MSB Specifications subject to change without notice 440 04 4413 03 25 Figure 15 Wiring Diagram 339241 2 Rev A ...

Страница 26: ...equence Gas valve and humidifier will not be turned on Inducer motor will start and remain on until the end of the blower test then off The following components are on for 10 15 seconds each individually hot surface igniter blower speeds FAN if present HEAT COOL Was there a previous status code Go to section below for the flashed status code Does the control respond to W Y1 Y Y2 and G 24V thermost...

Страница 27: ...ponent test Does the igniter glow orange white by the end of the 15 second warm up period Unplug igniter harness from control and repeat component test Check for 115V between connector P2 HSI and NEUTRAL L2 on the control Was 115V present for the 15 second period Check connections and retry If current is near typical value 4 0 6 0 A DC nominal and burners will not stay on replace control Clean fla...

Страница 28: ...nds after the gas valve GV is energized Simultaneously the electronic air cleaner terminal EAC is energized and remains energized as long as the blower motor BLWM is energized f Heat Off Delay When the thermostat is satisfied the R to W circuit is opened de energizing the gas valve GV stopping gas flow to the burners and de energizing the humidifier terminal HUM 24 VAC The inducer motor IDM will r...

Страница 29: ...ector box Condensate trap Condensate trap elbow Gaskets WARNING FIRE EXPLOSION ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in dangerous operation personal injury death or property damage Improper installation adjustment alteration service maintenance or use can cause carbon monoxide poisoning explosion fire electrical shock or other conditions ...

Страница 30: ...X ECM S Single stage T Two stage FEATURE B Base AFUE Efficiency E Extra AFUE Efficiency C Communicating D Dual Certified 2 pipe or 1 pipe R 2 pipe only S Single stage T Two stage N Standard L Low Nox FEATURE 040 40 000 BTU hr 060 60 000 BTU hr 080 80 000 BTU hr 100 100 000 BTU hr 120 120 000 BTU hr INPUT HEAT 14 14 3 16 17 17 1 2 21 21 24 24 1 2 CABINET WIDTH 10 1000 CFM max 14 1400 CFM max 16 160...

Отзывы: