R--410A QUICK REFERENCE GUIDE
S
R--410A refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement
components are designed to operate with R--410A
S
R--410A refrigerant cylinders are rose colored.
S
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
S
R--410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when
charging into suction line with compressor operating
S
Manifold sets should be minimum 700 psig high side and 180 psig low side with 550 psig low--side retard.
S
Use hoses with minimum 700 psig service pressure rating.
S
Leak detectors should be designed to detect HFC refrigerant.
S
R--410A, as with other HFCs, is only compatible with POE synthetic oils.
S
Vacuum pumps will not remove moisture from oil.
S
Do not use liquid--line filter driers with rated working pressures less than 600 psig.
S
Do not leave R--410A suction line filter driers in line longer than 72 hrs.
S
Do not install a suction--line filter drier in liquid line.
S
POE synthetic oils absorb moisture rapidly. Do not expose oil to atmosphere.
S
POE synthetic oils may cause damage to certain plastics and roofing materials.
S
Wrap all filter driers and service valves with wet cloth when brazing.
S
A factory approved liquid--line filter drier is provided with every unit.
S
Do NOT use an R--22 TXV.
S
Never open system to atmosphere while it is under a vacuum.
S
When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter
driers. Evacuate to 500 microns prior to recharging.
S
Do not vent R--410A into the atmosphere.
S
Observe all
warnings
,
cautions
, and
bold
text.
S
All indoor coils must be installed with a hard shutoff R--410A TXV metering device.