ICP iDRY Скачать руководство пользователя страница 7

 

iDRY Series Heatless Regenerated Dryers: IOM10003-C 

(Rev. A)

 

   

5

 

 

 

Technicians that service the machine must wear hearing and eye protection while servicing the dryer. Each 
employee must select a proper personal protection device (PPD) hearing protector such as earmuffs, ear 
canal caps or earplugs in order to prevent permanent hearing damage or loss.

 

 

Minimum Installation Requirements: 

 

Select a clean, dry room that is free of dust and protected from atmospheric disturbances. 

 

The location must be smooth, horizontally level, able to bear the weight of the dryer and vibration free 

 

Minimum ambient temperature of +40 °F 

 

Maximum ambient temperature of +120 °F 

 

Allow a clearance of at least 3’ on all sides of the dryer in order easily facilitate all maintenance needs 

 

The dryer is not required to be anchored to the supporting surface 

 

Coalescing pre-filter with drain must be installed  

 

The location of an air receiver tank will vary depending on compressor type and application conditions 

 

 

Incorrect installation may void warranty. 

 

NOTE:  All piping and electrical connections should be inspected prior to installation to ensure they have maintained 
their integrity during shipping and locating the dryer. 

 
First, make the initial connections as follows: 

 

 

1.

 

Inlet piping including an isolation valve 

2.

 

Outlet piping including an isolation valve 

3.

 

Coalescing pre-filter and particulate post-filter 

 

 

We recommend the dryer be installed with a 0.01 micron iPUR coalescing pre-filter at the inlet and a 1.0 micron 
iPUR particulate post-filter at the outlet.  It is recommended to install both 5.0 micron and  
1.0 micron filters upstream of the dryer in order to maintain the operational lifespan of the inlet filter to the 
dryer.    In  addition,  we  recommend  the  use  of  a  iMAT  zero  air  loss  drain  on  the  pre-filter  and  at  all  other 
condensate collection points, especially those upstream of the dryer. 
 

Locate the coalescing pre-filter as close to the dryer as possible while still maintaining sufficient space for routine 
maintenance and service.  Inlet air entering the dryer must pass through a coalescing pre-filter in order remove entrained 
condensate and oil to prevent fouling of the desiccant and maintain standard operation.  Any liquid condensate entering 
the desiccant bed will lead to overloading of the dryer, poor dew point performance and rapid deterioration of the 
desiccant material.  Any oil entering the desiccant bed may permanently reduce the capacity of the desiccant material. 

 

Desiccant dust traveling downstream of the dryer may cause contamination and/or accelerated wear to other 
components and equipment.  Therefore, a particulate post-filter should be provided to prevent desiccant dust from 
traveling downstream.  Activated alumina is considered a nuisance dust and proper precautions should be taken when 
handling desiccant (refer to applicable MSDS sheet). 

 

 

 

4.

 

IMPORTANT!

  Bypass piping is necessary.  Only bubble tight valves should be used. 

5.

 

Make the required electrical connections; please refer the type plate of your dryer.  The end user is 
responsible for providing short circuit protection for the dryer. 

6.

 

Points of access should be provided upstream and downstream of the dryer for periodic monitoring of 
dew point, pressure and temperature prior to finalizing the installation.  Taking periodic dew point 
measurements just downstream of the dryer gives the best indication of whether the dryer is 
performing optimally.  We recommend using METPOINT® instrumentation to ensure accurate 
measurements.

 

7.

 

All piping must be adequately supported and at least of equal size to the dryer connections. 

 

Содержание iDRY

Страница 1: ...his manual contains important information and should be made available to all personnel who operate and or maintain this product Carefully read this manual before attempting to operate or perform main...

Страница 2: ......

Страница 3: ...ERAL FUNCTION 7 3 1 Technical Data by Model Size 7 3 2 Correction Factors 8 3 3 General Function 8 3 4 Flow Diagram 9 3 5 Cycle Operation 10 4 PURGE VALVE ADJUSTMENT 11 5 START UP 12 5 1 Verification...

Страница 4: ...nt 21 8 5 Inlet and Exhaust Valve Repair 21 9 TROUBLESHOOTING GUIDE 22 10 MAINTENANCE AND SPARE PARTS 25 10 1 Required Maintenance Parts 25 10 2 Spare Parts 27 11 DISMANTLING OF THE DRYER 28 12 ELECTR...

Страница 5: ...and or operate the dryer In most countries states cities and or local municipalities the installation may only be carried out by a licensed installation company Inspections must be carried out by a q...

Страница 6: ...n of certain installation conditions in particular Voltage and frequency of the electrical power supplied Pressure temperature flow rate and chemical composition of the incoming compressed air Ambient...

Страница 7: ...to the dryer In addition we recommend the use of a iMAT zero air loss drain on the pre filter and at all other condensate collection points especially those upstream of the dryer Locate the coalescin...

Страница 8: ...istent dryer inlet flow provided by an upstream receiver while providing the most reliable shop air supply due to the downstream receiver Under no circumstances should the peak demand air flow exceed...

Страница 9: ...230 230 340 340 480 625 795 940 Outlet Pressure Dew Point F 40 Minimum Ambient Temperature F 40 Maximum Ambient Temperature F 120 Standard Inlet Air Temperature F 100 Maximum Inlet Air Temperature F 1...

Страница 10: ...used for the regeneration process and expelled along with the condensate through the silencers The saturated inlet air is cycled through each of the two desiccant beds in an alternating sequence where...

Страница 11: ...ficiency iPUR filters 0 01 micron filtration grade coalescing pre filter with differential pressure gauge and either a float drain or iMAT 1 0 micron filtration grade particulate post filter different...

Страница 12: ...terial dragging away the humidity through the PV B valve 2 and exits the silencers 3 At the end of this stage the adsorption material of vessel B is completely regenerated Step 3 The purge exhaust val...

Страница 13: ...below is based on the number of turns from the closed position 1 Loosen the screw using a flathead screwdriver or allen head 2 Turn the purge flow control valve clockwise until the stopping point the...

Страница 14: ...ts indicated on the data plate Installation precautions must be taken in order to limit the vibration that can occur during the operation of the dryer Therefore we recommend using flexible connecting...

Страница 15: ...running your compressed air system pressurized and the dryer bypassed and not yet pressurized 1 With the dryer bypassed and in isolation see page 14 2 SLOWLY open the inlet isolation valve allowing c...

Страница 16: ...ressurized suddenly This will cause degradation and dusting of the desiccant bed The dryer is designed for a maximum operating pressure of 150 psig as standard 6 ISOLATION AND SHUT DOWN PROCEDURES Use...

Страница 17: ...alve PV and IV The controller has two additional LEDs used to indicate power and service in the upper left corner of the display as shown by the corresponding icons During normal operation the power L...

Страница 18: ...ll Nema cycles as though the operating voltage has been interrupted i e as after RESET 7 4 Controller Outputs The controller outputs information two ways one to the controller display the other to the...

Страница 19: ...e is the time selected for step 3 in Section 3 5 The two DIP switches can be adjusted to four 4 regeneration times between 60 and 120 seconds in 20 second increments as follows 00 60 seconds factory s...

Страница 20: ...l flash red indicating that service is overdue 7 7 Power Requirements The controller operates on 100 120VAC 50 60Hz The units are shipped with an installed standard US 120 volt cord for convenience Be...

Страница 21: ...kes place correctly at the set cycle times Check that the tower pressure gauge of the regenerating tower reads 0 psig while the drying tower reads full line pressure ANNUALLY Replace the pre and post...

Страница 22: ...cement and maintenance such as the filter elements exhaust silencers and desiccant material NOTE The maintenance alarms reminders do not change the operation of the controller in any way 8 3 Fuses One...

Страница 23: ...ettling may be required in order to fit the specified fill amount into the tower Tank sizes may be the same for multiple models so do not be concerned if the tower is not entirely full 6 Desiccant tha...

Страница 24: ...lectric Check the operation of inlet and purge exhaust valves Ensure Control pilot air is delivering at 80 psi Ensure DIN connectors are properly attached to solenoid valves See controller troubleshoo...

Страница 25: ...exhaust troubleshooting Back pressure Purge muffler fouled Vessel screen Restricted purge piping Bad Purge Exhaust Valve Replace with new Empty towers remove screens and clean Clean See purge Exhaust...

Страница 26: ...ing Dirty element Electrical Differential pressure gauge Ensure proper dryer sequence Contaminated filter replace element Faulty electrical signal Clean check and or replace Controller Defective No po...

Страница 27: ...E 12S 00 iELE 15S iELE 15S 00 iELE 18S iELE 18S 00 iELE 20S iELE 20S 00 iELE 25S iELE 25S 00 Post filter Element 1 0 m iELE 07F iELE 07F 00 iELE 10F iELE 10F 00 iELE 12F iELE 12F 00 iELE 15F iELE 15F...

Страница 28: ...802 4026888 1 Exhaust Valve Actuator 4026416 4026889 1 Exhaust Valve Actuator 4020804 4026890 2 Exhaust Valve Actuator 4020806 4026891 Service Seal Kit Service Seal Kit 4027898 1 Service Seal Kit 4027...

Страница 29: ...rol Valve 1 4020765 1 Purge Flow Control Valve 4020766 Electronic Controller MINI Electronic Controller PLC 4026540 Solenoid Valve Assembly Complete MAC Solenoid Valve Assembly 4024046 Tower Pressure...

Страница 30: ...g Aluminum Epoxy paint Filter cartridge Filtering material PVC Oil Solenoid valve Bronze Steel Techno polymer PVC Condensate Drain PVC Aluminum Steel Bronze Silencers Aluminum Stainless steel Safety V...

Страница 31: ...of process air through the dryer Safety Relief Valves Valves on each tower to protect the vessels from overpressure situations The setting is indicated on each valve Purge Exhaust Silencer Installed t...

Страница 32: ......

Страница 33: ...ated Dryers IOM10003 C Rev A Independent Compressor Partners LLC P O Box 206 Jeffersonville IN 47131 www i compressorpartners com Subject to technical changes without prior notice errors not excluded...

Отзывы: