5. Healthy Dehumidification
• When the dehumidification operation input by the remote control is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C
≤
Intake Air Temp
➲
25°C
24°C
≤
Intake Intake Air Temp<26°C
➲
Intake Air Temp-1°C
18°C
≤
Intake Intake Air Temp<24°C
➲
Intake Air Temp-0.5°C
Intake Air Temp<18°C
➲
18°C
• While in compressor off, the indoor fan repeats low airflow speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat.
Compressor ON Temp.
➲
Setting Temp+0.5°C
Compressor OFF Temp.
➲
Setting Temp-0.5°C
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
- 18 -