ZT-2055 - 8-channel DI
DAQ module - QuickStart (Dec/2019)
ICP DAS USA, Inc.
| 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
9
7
Communication Test
Once the ZT-2000 I/O device has joined the ZigBee network, the signal quality can
be comfirmed by monitoring the status of the ZigBee Net LED indicators. If the LED
indicator shows a steady light, communication with the ZT-2000 I/O device has been
successfully established for data acquisition and control.
ICP DAS also provides the “DCON Utility”, which can be used to simulate
DCON/Modbus communication. This software can also be used to verify the device
settings and ZigBee I/O functions.
※
The DCON Utility can be dowmload from:
http://ftp.icpdas.com/pub/cd/8000cd/napdos/driver/dcon_utility/
Simulate I/O channel operating via using DCON Utility
1.
Launch DCON Utility and select the correct COM Port settings to connect the
ZigBee Coordinator (ZT-2550/ZT-2570).
2.
Clicking “Search” button will start searching which ZT-2000 I/O device is in the
same ZigBee network.
3.
If there is any ZT-2000 I/O devices displayed, double clicking the “module
name” will start the I/O channels operated platform.