Setting up the ZT-2000 I/O Device
3.1
Introduction to the Configuration
Parameters
A.
The “ZB PID” parameter is the group identity for a ZigBee network, and must be
same for all devices in the same ZigBee network.
B.
The “Node ID” parameter is the individual identity of the specific ZigBee module, and
must be unique for each device connected to the same ZigBee network.
C.
The “ZB Channel” parameter indicates the radio frequency channel, and must be set
to the same value as other modules on the same ZigBee network.
ZB Channel
0x00
0x01
……
0x0F
Frequency (MHz)
2405
2410
……
2480
※
ZB channels 0x04, 0x09, 0x0E or 0x0F are recommended because they do not overlap with
Wi-Fi frequency band.
D.
Protocol/Application Mode:
When implementing custom programs based on different protocols, the following
application mode(s) are recommended in order to ensure optimal performance.
User Program Protocol
ZT-2000 I/O
ZT-2550
ZT-2570
DCON
DCON
Transparent
Transparent
Modbus RTU
Modbus RTU
Transparent
Modbus Gateway
Transparent
Modbus Gateway
Modbus TCP
Modbus RTU
------
Modbus Gateway
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
802.11b/g
ZB Channel 1
802.11b/g
ZB Channel 6
802.11b/g
ZB Channel 11
802.11b/g ZB Channel (North America)
802.15.4 ZB Channel
2400
MHz
2485