ICP DAS, ZT-2017 and ZT-2017C AI Series User Manual, Version 1.0.1
Page 35
Copyright © 2012 by ICP DAS Co., Ltd. All Rights Reserved.
6.2.3
%AANNTTCCFF
Description
This command is used to set the configuration of a specific module.
Syntax
%AANNTTCCFF[CHECKSUM](CR)
%
Delimiter character
AA
The address of the module to be configured in hexadecimal format (00 to
FF)
NN
The new address of the module in hexadecimal format (00 to FF)
TT
00 (Reserved)
CC
0A (Reserved)
FF
The command used to set the data format, checksum, and filter settings
(See Section 4 for details)
Response
Valid Command
!AA[CHECKSUM](CR)
Invalid Command ?AA[CHECKSUM](CR)
!
Delimiter character to indicate a valid command
?
Delimiter character to indicate an invalid command
AA
The address of the responding module in hexadecimal format (00 to FF)
There will be no response if the command syntax is incorrect, there is a
communication error, or there is no module with the specified address.
Examples
Command %0320000A80
Response !03
In Normal mode, the address 0x20 is saved to the EEPROM and the data format
for module 03 is set to 80 (50 Hz rejection). The module returns a response
indicating that the command was successful.
Command %0320000A80
Response !20
In Software Configuration mode, the address 0x20 is saved to the EEPROM and