WF-2000 Series AIO
User’s Manual (RevB1.0, Oct./2016) ------------- 36
Enable / Disable the open-wire detection for thermocouple.
CJC Enable
Enable / Disable the CJC (Cold-Junction Compensation).
CJC Offset
Setting the CJC offset value for all AI channels. The offset
value is used to add or subtract the reading value.
Changing of this value will not affect calibration, but will
affect the reading value of temperature type.
Note: The CJC offset can be any in the range of -30.00 to
+100.00 °C.
Polling Interval
This value is the period to poll data to the WF-2000 I/O
module.
Note: The valid value is 100 ~ 5000ms.
Show Hex
Convert the I/O value from decimal to hexadecimal.
RSSI
This area will display the signal strength information by
RSSI value and LED indicator when press the "Get" button.
Table
3-1 Signal Strength Information Display Table
Signal Strength LED Indicator
LED Status
RSSI value
Signal strength
1 ~ 40
High
41 ~ 60
Medium
61 ~ 80
Low
0
Bad or No Signal