WF-2000 Series Wi-Fi I/O
User’s Manual (Ver. 1.0, Sep./2012) ------------- 51
5.3.2 WF-2060 I/O and Counter Address Mapping
Table 5-9:
(0xxxx) DO address
Begin Address
Points
Descriptions
Range
Access Type
0
(0x00)
0~5
Digital Output
0=OFF, 1=ON
R/W
10
(0x0A)
0~5
Clear Digital
Counter
1=Clear
W(Pulse)
Table 5-10:
(1xxxx) DI address
Begin Address
Points
Descriptions
Range
Access Type
0
(0x00)
0~5
Digital Input
0=OFF, 1=ON
R
Table 5-11:
(3xxxx) AI address
Begin Address
Points
Descriptions
Range
Access Type
50
(0x32)
0~11
(2 points/ Each
Channel)
Digital Counter
0~4294967295
R
Table 5-12:
(4xxxx) AO address
Begin Address
Points
Descriptions
Range
Access Type
247
(0xF7)
0
Reset System
1= Reset System
247= Restore to
Factory Default
Settings
W