background image

ICP DAS Co., LTD 

PM-4324 Series Quick Start V1.3 

Page 2 

2. 

Installation 

Please use the soft dry clothes to clean the instrument. 
Please do not use any chemical or detergent or volatile solvents to clean 
the instrument, in order to avoid any possibility of the cover damage. 

 

  Products come with external split type clip-on CT’s. Disconnect the CT’s 

or use other CT’s is highly prohibited. 

  Please read this operation manual carefully before using. 

  Please re-confirm the measure position. 

  Reconfirm the RST (ABC) phase sequence of the power system. 

  Meter auxiliary power for PM-4324 series is AC +100V ~+240V.   

2.1. 

Voltage Input 

1.  PM-4324 series: Input Voltage up to 500V. 

 

For any higher Input Voltage large than 500V, please add the PT (power 
transformer), and Change PT RATIO setup. 

2.  Confirm the RST (ABC) phase sequence. 

2.2. 

Current Input 

1.  The external CT’s are fragile, please handle with care. 
2.  The current input of PM-4324 series is in mA range. 

Only the ex-factory attached CT’s can be used. The other CT’s, 
for example, from panel will damage the instrument due to its 
large current (around 5A) 

3.  When more than one smart meter (PM-4324 series) are installed, please 

do not disconnect the CT with its original meter and mix use with each 
other. Since each set of smart meter (PM-4324 series) and its attached 
split type clip-on CT are calibrated set by set. The mix use may cause 
wrong measurements. 

4.  To install CT’s correctly, please ensure the CT lines sequences is right 

before clip the CT’s onto the power cable of the monitoring equipment. 
(Detail will be found in next section) 

5.  When measuring the current, the secondary circuit of a CT should 

never be opened when a load is passing through its primary. Make 
sure you always open the CT clip to detach the CT before removing 
the terminal lines. Otherwise, it will cause severe injury.   

6.  Please handle with extra care, especially when the operation space of 

CT’s is limited. 

7.  The current direction must follow K-L marked on CT’s. 

8. 

Φ16

Φ24 use 200A CT

Φ24

Φ36 use 300A CT or 400A CT

 

9.  The maximum current value cannot exceed the CT rating. 

 

 

Содержание PM-4324 Series

Страница 1: ...any damage resulting from the use of this product ICP DAS reserves the right to change this manual at any time without notice The information furnished by ICP DAS is believed to be accurate and relia...

Страница 2: ...ly the ex factory attached CT s can be used The other CT s for example from panel will damage the instrument due to its large current around 5A 3 When more than one smart meter PM 4324 series are inst...

Страница 3: ...sign on CT s follows current flow direction K L Note it must be in the same direction Connect the voltage input terminal N C B A for PM 4324 in the three phase order as follows on N C B A Attention p...

Страница 4: ...ICP DAS Co LTD PM 4324 Series Quick Start V1 3 Page 4 2 5 Wiring 1P2W 1CT PM 4324 1P3W 2CT PM 4324...

Страница 5: ...ICP DAS Co LTD PM 4324 Series Quick Start V1 3 Page 5 3P3W 2CT PM 4324 3P3W 3CT PM 4324 DIP switch Wiring mode SW 9 SW 10 3P3W 3CT OFF ON...

Страница 6: ...ICP DAS Co LTD PM 4324 Series Quick Start V1 3 Page 6 3P4W 3CT PM 4324 DIP switch Wiring mode SW 9 SW 10 3P4W 3CT ON ON...

Страница 7: ...3 OFF ON OFF OFF OFF OFF 4 ON ON OFF OFF OFF OFF 5 OFF OFF ON OFF OFF OFF 6 ON OFF ON OFF OFF OFF 7 OFF ON ON OFF OFF OFF 8 ON ON ON OFF OFF OFF 9 OFF OFF OFF ON OFF OFF 10 ON OFF OFF ON OFF OFF SW7...

Страница 8: ...8 Otherwise the tM SG4 or SG 785 should be added to provide the bias All ICP DAS controllers and converters provide the bias 2 8 Ethernet setting Ethernet default settings IP Address 192 168 255 1 Su...

Отзывы: