PM
-
3033 User’s Manual v1.20
Last Revised:Mar. 2017 Page: 62
Copyright © ICP DAS Co., Ltd. All Rights Reserved.
E-mail: [email protected]
3
Freq _c
INTEGER32
RO
0
4
Freq _avg
INTEGER32
RO
0
320Ah 0
largest sub-index supported for
object
UNSIGNED 8
RO
2
1
VTHD
(Phase set by
Harmonic Phase
Select Register)
INTEGER32
RO
2
ITHD
(Phase set by
Harmonic Phase
Select Register)
INTEGER32
RO
320Bh 0
largest sub-index supported for
object
UNSIGNED 8
RO
6
1
PT Ratio
UNSIGNED 16 RW
100
2
CT Ratio
UNSIGNED 16 RW
1
3
Software Wiring
(Only work when SW9-SW10 is all off)
1: 1P2W
2: 1P3W
3: 3P3W2CT
4: 3P3W3CT
5: 3P4W3CT
UNSIGNED 16 RW
1
4
Energy Absolute Accumulated
Mode
0: Enable
1: Disable
UNSIGNED 16 RW
0
5
H Phase Select
0: Disable
1: Phase A
2: Phase B
3: Phase C
UNSIGNED 16 RW
0
6
Display Voltage
0: Automatic
1: Show as Vln
2: Show as Vll
UNSIGNED 16 RW
0