Q: How to Get M-7059 Data through Modbus TCP with tGW-715? 

 

 

A: For detailed configuration steps, please refer to the following: 

 

Before self-test, please ensure that your PC has workable network settings. 

Step 1: Connect the tGW-715 module with M-7059 device using the RS-485 bus. 

1.

 

Connect both the tGW-715 and your computer to the same sub network or the same Ethernet Switch 

and power the tGW-715 on. 

2.

 

Connect the

 

M-7059 device to COM1 (RS-485 bus) on tGW-715. 

3.

 

Supply power (+10 V

AC

 ~+80 V

AC

) to DI0 (+/-) pins on M-7059 device for channel 0 of DI is ON. 

4.

 

Supply power (+10 V

DC

 ~+30 V

DC

) to the M-7059 device. 

 

 

 

 

 

 