Q: How to Get M-7059 Data through Modbus TCP with tGW-715?
A: For detailed configuration steps, please refer to the following:
Before self-test, please ensure that your PC has workable network settings.
Step 1: Connect the tGW-715 module with M-7059 device using the RS-485 bus.
1.
Connect both the tGW-715 and your computer to the same sub network or the same Ethernet Switch
and power the tGW-715 on.
2.
Connect the
M-7059 device to COM1 (RS-485 bus) on tGW-715.
3.
Supply power (+10 V
AC
~+80 V
AC
) to DI0 (+/-) pins on M-7059 device for channel 0 of DI is ON.
4.
Supply power (+10 V
DC
~+30 V
DC
) to the M-7059 device.