iSN-101/104 User Manual
- 37 -
00290*
Alarm status of open wire for iSN-101. Write 1 to clear latched alarm. R/W
00289 ~
00292
Leak alarm status of leak sensor 0 to 3 for iSN-104. Write 1 to clear
low latched alarm.
R/W
00293 ~
00296
Open wire alarm status of leak sensor 0 to 3 for iSN-104. Write 1 to
clear latched alarm.
R/W
00321 ~
00324
Enable/disable leak alarm of leak sensor 0 to 3 (iSN-101:0)
R/W
00322*
Enable/disable alarm of open wire (for iSN-101 only)
R/W
00325 ~
00328
Enable/disable open wire alarm of leak sensor 0 to 3
(for iSN-104 only)
R/W
00337 ~
00340
Leak alarm type, momentary or latched, of leak sensor 0 to 3
(iSN-101:0)
R/W
00338*
Alarm type, momentary or latched, of open wire (for iSN-101 only)
R/W
00341 ~
00344
Open wire alarm type, momentary or latched, of leak sensor 0 to 3(for
iSN-104 only)
R/W
00385 ~
00388
Write 1 to clear high latched analog input value of sensor 0 to
3(iSN-101:0)
W
00417 ~
00420
Write 1 to clear low latched analog input value of sensor 0 to
3(iSN-101:0)
W
* iSN-101 for firmware version A103 and later only
DIP Switch setting
1 Protocol
ON: DCON, OFF: Modbus RTU
2 Configuration
ON: by software, OFF: by hardware
3 Address
ON: added by 16, OFF: added by 0
4
INIT mode
ON: INIT, OFF: Normal
5
Sound
ON: turn on, OFF: turn off (for iSN-104 only)
Base address: 96 (0x60)