4-22
Getting Started:
PAC-5007(P)/5107(P)/5207/5307 Ver. 1.0, 07/2010 ICP DAS
NG
If the message in the "ISaGRAF Debugger" says "Disconnected", it means the connection
between PC and μPAC-5x07(P) is failed.
The most common causes of connection failure are the COM Port between each other is
not plugged in or the settings of communication parameters are not correct. When this
occurs, please follow the following steps to troubleshoot the problem:
1.
Ensure that the communication cable between PC and μPAC-5x07(P) is plugged well.
2.
, verify the COM Port settings.
3.
Refer to
step 10; verify the NET-ID, Baud rate settings.
If the NET-ID or Baud rate of PAC does not match the PC settings, recommand you to
refer the
If you want to modify the NET-ID or Baud rate of PAC, please refer to
Downloading the Example LD Program:
Click "Download" button in the "ISaGRAF Debugger" window, then click on "ISA86M: TIC
Code for Intel" and then click "Download" button. (As diagram below)
Now, the program is downloading to the controller and you will see the download
progress in the “ISaGRAF Debugger” window.
The connection is not success.
1.
2.
If there is no
“
ISA86M: TIC code for
Intel
”
, please refer to section 4.2 and
compile again.