I-8014W API User Manual, v1.0.1, June 2011
Copyright © 2011 ICP DAS Co., Ltd. All Rights Reserved. E-mail: [email protected]
88
Troubleshooting
This chapter discusses how to solve the problem you may meet.
This chapter contains:
How to verify the AI function on WinCE or WES unit? (See
page 88
Service-request requirement (See
page 92
Why does the data read from I-8014W seem unstable? (See
page 92
How to solve FIFO LATCHED error (-6)? (See
page 933
)
How to verify the AI function on WinCE or WES
unit?
If the data read from the I-8014W is inconsistent with the input signal, and you would
like to confirm the input function, pac_i8014W_Utility.exe may help you. The utility is
for using I-8014W on
WinCE and WES controller only
and is located in the I-8014W
C # demo program for the controller. (See
Demo Programs Location, page 12
Step1
. Wire a stable signal to I-8014W.
a
. Wire your input signal according to the Differential or single-ended Jumper
setting. (See
b
. The input range could be from +10V to -10V.
c
. Plug the I-8014W on the slot of your controller and turn on the Windows
platform controller.