I-7530A-MR Modbus RTU to CAN Converter Quick Start User Guide (Version 1.0, May/2011)  ------ 6

 

Baud rate

 

:  115200bps

 

Data bits

 

:  8 

Stop bits

 

:  1

 

Parity

 

:  None

 

Checksum :  No

 

 
Step8: Set the CAN baud rate of the I-7530A-MR_A. Here, use 125 kbps 

for CAN baud, and uncheck the “Enable CAN Filter” item (For 
more information about CAN Filter configuration, please refer to 
the section 3.4 of the user manual). 

Step9: Set the Device ID of the I-7530A-MR_A and I-7530A-MR_B as 1 

and 2 respectively. Here the “Specific CAN ID” field does not be 
used (For more information about Modbus RTU configuration, 
please refer to the section 5 of the user manual) 

Step10: Click the “Setting” button to save these CAN/COM parameters 

into the EEPROM of the I-7530A-MR_A. 

Step11: Repeat Step 1 ~ Step 9 to configure the I-7530A-MR_B converter 

with the same configurations as the I-7530A-MR_A. 

 

4.   Testing the I-7530A-MRs 

 

Step1: Turn off the DC power connected with these two I-7530A-MR 

modules. 

Step2: Set the Init/Normal switches on the back of the I-7530A-MR A and 

I-7530A-MR_B to the “Normal” position. Then, turn on the DC 
power. The CAN LED and UART LED of the I-7530A-MR_A and B 
will be turned off.  It means these two I-7530A-MR converters are 
working in the operation mode. 

Step3: Run the UART2CAN Utility twice. Then duplicate I-7530A-MR 

Utility dialogs will be displayed on the PC’s screen. Assume that 
one is named as Utility_A and the other is Utility_B.  

Step4: Select the proper COM port parameters and configure the RS-232 

COM1 and the RS-232 COM2 of the PC. The COM1 and COM2 
ports of the PC will be used for connecting with the I-7530A-MR_A 
and I-7530A-MR_B respectively. Then change the communication 
mode of Utility_A and Utility_B to Modbus RTU mode. The two 
Utility dialogs are similar with the following picture. 

Содержание I-7530A-MR

Страница 1: ...ction The goal of this manual is focused on helping users to quickly familiarize themselves with the I 7530A MR module and the data exchanged between RS 232 485 422 and CAN communication interfaces He...

Страница 2: ...Installation Users need to make a hardware connection between the two I 7530A MR modules before the application The details of this are illustrated below Step1 Set up the 120 terminator resistor of t...

Страница 3: ...connection Connect the RS 232 ports of the I 7530A MR_A and I 7530A MR_B to the RS 232 COM1 and COM2 of the PC by using the attached cable CA 0910 respectively You can use the attached cable CA 0910...

Страница 4: ...set the Init Normal switches to the Init position and hold it at least 3 seconds The CAN LED and UART LED of the I 7530A MR_A will flash approximately once per second That means that the I 7530A MR i...

Страница 5: ...ul the UART2CAN Utility will show the communication information of the I 7530A MR_A module as shown in the following figure Step6 Set the communication mode of the I 7530A MR_A Here use Modbus TRU mod...

Страница 6: ...rter with the same configurations as the I 7530A MR_A 4 Testing the I 7530A MRs Step1 Turn off the DC power connected with these two I 7530A MR modules Step2 Set the Init Normal switches on the back o...

Страница 7: ...U command and send it out through the PC RS 232 COM1 port After the I 7530A MR_A receives this command it will convert the Modbus RTU message to the CAN message and send it to the CAN network While th...

Страница 8: ...I 7530A MR Modbus RTU to CAN Converter Quick Start User Guide Version 1 0 May 2011 8 Utility A 5 9 8 7 6 Utility B...

Отзывы: