Module test and configuration
Step 1: INIT switch Operation
1.
Find out the INIT switch( back of the module),
and turn to INIT.
2.
Reboot the module
Step 2: Install & Run DCON Utility
1.
Please Install DCON Utility first
You can find the software in the CD.
CD path:
<Driver>:\napdos\driver\dcon_utility\
Web link:
http://ftp.icpdas.com/pub/cd/8000cd/napdos/driver/dcon_utility/
2.
Run DCON utility
Step 3: Set search configuration & search module
Step 4: Select Module for testing and configuration
1.
Click “COM Port”
2.
Assign the communication information and click
“OK”
Module Default Setting
COM Port
Refer converter Port Number
Baud Rate
9600
Protocol
DCON for I-7000
Modbus RTU for M-7000
Parity Option
N,8,1
3.
Click “Search” and select “Start Searching”
Software will search the modules from COM Port
4.
Click “Search“ and select “stop searching”
Manual stop when the modules searched
Note:
When no module can be searched, please check the
wire and communication information
Select COM Port Number
Double click “select module”
Page 3