Server IP: VxServer IP or domain name.
Server Port: VxServer port number.
Heartbeat Time: The time interval for sending heartbeat packets to VxServer.
[1]
Device ID: The unique ID used to identify the device.
Alias: The alias of the device. The maximum length is 8 characters.
Time Interval: The time interval for sending serial port data to VxServer.
[2]
Data Length: The data length of the serial port data sent to the VxServer.
[3]
Modbus TCP to RTU: Modbus TCP to Modbus RTU gateway function.
“Port1” = “COM1 (RS-232)”
“Port2” = “COM2 (RS-485)”
“Port3” = “COM3 (RS-485)”
Default Baudrate: This value depends on your serial device.
“115200” means baud rate is 115200 bps
“57600” means baud rate is 57600 bps
“38400” means baud rate is 38400 bps
“19200” means baud rate is 19200 bps
“9600” means baud rate is 9600 bps
Default Format: The configuration of "data bit", "parity" and "stop bit".
Data bit support
“8” means “8-bits”
“7” means “7-bits”
Parity bit support
“N” means “None”
“O” means “Odd”
“E” means “Even”
Stop bit support
“2” means “2-bits”
“1” means “1-bit”
Enable Function: Whether to Enable this function. This setting will run after reboot.
[1] VxServer will detect the disconnection in advance and terminate the connection.
[2] If the time interval between two serial data is greater than this value, the data will be
divided into two network packets. If there is not enough time interval, but the data
length exceeds
the “Data Length”, the data is still divided into two network packets.