Firmware Update via Ethernet (Ver. 1.0/Sep. 2015)
Page:
4
Step 8: Set the
“Init Switch”
on the ET-2200 module to the
“Init”
position.
Step 9:
Power-on reset
the ET-2200 module in
“Init Mode”
to initiate the update.
Step 10: Confirm that the two MAC addresses (factory-default) listed in the Command Prompt
window,
“Waiting request from MAC x.x.x.x”
and
“BOOTPREQ from MAC: x.x.x.x”
,
are the
same, as indicated in the image below. If these addresses do not match, the update cannot
Step 11: Once the update is complete (i.e., when the
progess indicator reaches 100%), set the
“Init Switch”
to the
“Run”
position.
Step 12:
Power-on reset
the ET-2200 module to
operate the module in
“Run Mode”
.
Firmware update begins
Request received from this MAC Address
Waiting for a request from this MAC Address