EIP-2019 8-Channel Thermocouple Analog Input EtherNet/IP Module
- QuickStart (Mar/2019)
ICP DAS USA, Inc.
|
www.icpdas-usa.com
| 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
III. I/O Wire Connection
Voltage Input
Thermocouple Input
4
Using the EIP-2000 Utility
1.
Double click the
“EIP-2000 Utility”
shortcut on the desktop.
2.
Click the “Network Scan” button to search your EIP-2000 modules(Figure 4-1).
Figure 4-1 EIP-2000 Utility network scan
3.
Click the
EIP-2019 or other EIP-2000 modules
on the device list below to open the
configuration dialog of
EIP-2000
. Each EIP-2000 module has its own configuration
interface. Please refer to Figure 4-2.
(1)
In the
“Analog Input Status”
, users can select AI type of every channel.
(2)
In the
“AI Parameters”
, users can select the AI filters and AI representations here.
There are two different AI filters 50Hz and 60Hz. The selection of filters must
correspond with the frequency of AI sensors. Users have to check what are the
requirements of AI sensors. We provide two AI representations engineer and hex. If
users change the AI representation, all AI status will become to it.
(3)
In
“CJC Settings Users”
can set the CJC enable or not by the CJC Switch, and adjust
CJC value with CJC Offset.
(4)
If the network settings have been changed, please click the
“Update
Network
Settings”
button to update the configuration and reboot the module.