2.1 %AANNTTCCFF
z
Description
: Set the configuration of module.
z
Syntax
:
%AANNTTCCFF[chk](cr)
% is a delimiter character
AA=2-character HEX module address, from 00 to FF
NN=new AA
TT=input type code, refer to Sec. 1.9
CC=baud rate code, refer to Sec. 1.9
FF=status code, refer to Sec. 1.9
[chk]=2-character checksum, if checksum disable
Æ
no [chk]
(cr)=0x0D
z
Response
: valid command
Æ
!AA[chk](cr)
invalid
command
Æ
?AA[chk](cr)
no response
Æ
syntax error or address error
or communication error
! is a delimiter character indicating a valid command
? is a delimiter character indicating a invalid command
AA=2-character HEX module address
[chk]=2-character checksum, if checksum disable
Æ
no [chk]
(cr)=0x0D
z
Example
:
command: %0102530600(cr)
response : !02(cr)
command: %0202530600(cr)
response : !02(cr)
address 01 is configured to a
new address 02, 9600BPS
Refer to
“
I-7000 Bus Converter User Manual
”
chapter-5
for the following functions:
z
module status unknown
(Sec. 5.1),
change address
(Sec. 5.2)
z
change baud rate
(Sec. 5.3),
checksum enable/disable
(Sec. 5.4)
Change to 9600BPS
.
I-7083/7083D/7083B/7083BD User Manual (V 1.1, Dec/2007) ------------------ 25