to the PROFIBUS specification up to 32 stations are allowed per segment. A
repeater has to be used to link the bus segments.
2.3.3 CANopen terminator resistor settings
In order to minimize reflection effects on the CAN bus line, the CAN bus lines
have to be terminated at both ends by two terminal resistances. Based on the
ISO 11898-
2 spec, each terminal resistance is 120Ω (or between
108Ω~132Ω).
The length related resistance should have 70 mΩ/m. Users
should check the
resistances of their CAN bus, before they install a new CAN network as figure 7,
8.
Figure 7 CANopen terminator resistor
Figure 8 CANopen terminator resistor