Technical Specifications

Installation

Max. Working Temperature

190°F | 88°C

Max. Working Pressure | Non-Shock

145 psi | 10 bar

Relay

SPST Reed Switch | NO | NC | Adjustable

Protection Class

IP 65 | NEMA 4X

Max. Contact Current

1.5A

Max. Power Supply

85 VDC | 250 VAC

Body

PP

O-Ring

Viton

General

General Installation Instructions

When  choosing  the  installation  site,  ensure  that  the  specified  limit 
values (see "Technical Specifications") are not exceeded.

Select suitable measures to prevent the medium from freezing.
If the flow switch is to be used in ambient temperatures of < 39.2 °F, 
do not carry out any operation beforehand with pure water, e.g. a test 
run. Residual water in the flow switch can result in frost damage.

Firstly, clean the pipe system in which the flow switch is to be installed 
and remove any magnetic particles, e.g. welding residue.

The straight in- and outlet pipe (in front of and behind the flow switch) 
has to be at least 5 x ID.

The  nominal  installation  position  of  the  flow  switch  is  an  "upright 
standing position" in horizontal pipework.

The  switches  should  only  be  installed  in  a  vertical  position,  deviation 
max. 45 (Fig. 1).

Please  contact  the  manufacturer  if  other  installation  positions  are 
desired.

Please  make  sure  that  there  are  no  external  magnetic  fields  in  the 
immediate  vicinity  of  the  flow  switch,  since  these  can  impair  device 
functioning (Fig. 2).

There is an arrow on the flow switch. Ensure that this arrow is parallel 
with the pipe shaft and is facing in the direction of flow
during installation (Fig. 2).

The brass and Plastic union nuts ¾" BSP have a tightening torque of 
18.439 ... 22.127 ft lb.

The plastic union nuts have a tightening torque of 5.163 ... 5.901 ft lb.

Fig. 1

max. 45°

Fig. 2

www.iconprocon.com | [email protected] | 905.469.9283

05

Plastic Flow Switch

FES SERIES

Содержание truflo FES Series

Страница 1: ...Plastic Flow Switch FES SERIES Operating Manual www iconprocon com sales iconprocon com 905 469 9283 Plastic Flow Switch FES SERIES...

Страница 2: ...ciple Pump Protection Technical Specifications Installation Electrical Connection Dimensions Warranty Returns and Limitations 03 04 04 04 05 05 06 08 09 Table of Contents www iconprocon com sales icon...

Страница 3: ...r the respective literature it is the responsibility of the customers to determine the suitability of the product for the specific application The flow switches are state of the art devices This conce...

Страница 4: ...ir device functioning The technical data of special versions customised versions can deviate from the details in these instructions Please observe the details on the type plate Caution Danger of death...

Страница 5: ...any magnetic particles e g welding residue The straight in and outlet pipe in front of and behind the flow switch has to be at least 5 x ID The nominal installation position of the flow switch is an u...

Страница 6: ...s 7 and subsequently connect the wires as displayed in the connection diagram see Fig 4 Danger of death due to electrical voltage Work on electrical installations may only be carried out by qualified...

Страница 7: ...ion the switching unit until the red or white arrow are visible at the entry of the switching contact guide for a desired make contact or break contact respectively You can use the arrow length to mak...

Страница 8: ...005 8 NPT NPT NPT NPT NPT NPT 20 30 40 70 110 120 1 2 3 6 4 8 8 4 5 5 5 8 11 18 24 2 0 9 1 9 2 9 5 5 4 6 7 5 4 5 7 8 10 17 5 24 27 27 27 27 27 27 52 52 52 112 112 112 12 X 20 12 X 20 12 X 20 12 X 80 1...

Страница 9: ...cted to electrical mechanical or chemical damage due to improper accidental or negligent use 3 have been modified or altered 4 anyone other than service personnel authorized by Icon Process Controls L...

Страница 10: ......

Отзывы: