iCON
iSOLAR 3”
PDP Instruction Manual
7
7. Electrical Connections cont.
Locate the solar array and the controller as close to your water source as possible.
iSolar PDP pumps consume only low levels of input power, so it is important that
energy losses are minimised to ensure performance expectations are met.
808691 - BIA-PDP3 SOLAR250
808692 - BIA-PDP3 SOLAR370
808694 - BIA-PDP3 SOLAR750
If intending to extend the power cable, use this chart as a guide. Exact cable size will vary according to the
input characteristics and technical specifications of the solar panel. Calculations assume 5% loss.
Solar Panel Input
Cable length (Up to
’x’ Meters)
Watts
Panels
Max
VOC
Vmpp
Amps
< 10
< 25
< 30
< 50
< 75
< 100
CROSS SECTION MM
2
300
1 x 300
48V
35
10
2.5
2.5
2.5
6
10
10
600
2 x 300
96V
70
10
2.5
2.5
2.5
2.5
4
6
900
3 x 300
150V
105
10
2.5
2.5
2.5
2.5
2.5
4
1200
4 x 300
180V
140
10
2.5
2.5
2.5
2.5
2.5
4
Total cable length measured from the solar array to the pump motor.
The Max Voc (V) and Max Current (A) capabilities of the motor and the controller must be
respected.
Fitting additional panels or incorrectly rated panels will cause serious harm or
irreparable damage to the controller and motor voiding warranty
iSOLAR PDP3-250 power is supplied by a single panel.
iSOLAR PDP3 models 370 and 750 - panels must be wired in series.
30m
51m
96m
Total acceptable cable length per
model, from panels to pump motor,
when using 2.5mm
2
cable, to keep
energy losses less than 10%