6.3 Mode of NPN Pulse Output TKP | TKM Models
ALt = 1
ALt = 0
ALt = 3
ALt = 2
Current Value = Flow Rate
Hys = Hysteresis ACTS Lika Buffer ± Around Pulse Output (Measured in GPM)
SV = Selected Value = Programmed Value (Customer)
CV < SV ON: CV > SV + HyS OFF
CV > SV ON: CV < SV - HyS OFF
SV + HyS > CV > SV - HyS OFF: CV > SV + HyS or CV < SV - HyS ON
SV + HyS > CV > SV - HyS ON: CV > SV + HyS or CV < SV - HyS OFF
DESCRIPTION
ALT NO.
6.4 K-Factors for TK
72
124
19
54
4.7
10.3
2.1
LPM
¾"
½"
1 ½"
1"
3"
2"
4"
Size
274
471
72
171
18
39
8
GPM
6.5 Programming TKS Model Only
F
SET
(Together)
OPERATION
DISPLAY
STEPS
Home Screen
Press +
Step-1
TKS Series Only
Power Up Flow Meter with DC Power
000.0
(HOLD)
24V DC POWER ONLY
F
SET
Flow Meter
TKS
Alarm
GPM
Programming
Lock
Output
Press
Step-2
Programming Lock - Out Secure Feature
Lk = 10 (Unlocked Status) -
(Default)
Changing Number will Lock Flow Meter
LK.10 (Default)
10 = Unlocked
If any other Number is entered the Programming will be restricted
F
SET
Flow Meter
TKS
Alarm
GPM
No Programming
Required K Value
Press
Step-3
K-Factor Range : 0.1-999.9 (Depends on Meter Size - Factory Pre- Programmed)
K Value Preset (Do Not Change)
F
SET
Flow Meter
TKS
Alarm
GPM
Programming
Units
of Flow
Press
Step-4
Program Flow Units 0,1,2
Ut = 0 : (LPM)
Ut = 1 : (GPM)
(Default)
Ut = 2 : {Kiloliter (KL)}
F
SET
Flow Meter
TKS
Alarm
GPM
Programming
Communication
Output Type
Press
Step-5
Programming NPN Pulse Output
con.E - Output = 1 Pulse / Gal
con.F - Paddle Pulse Output 5KHZ MAX-Remote Display
con.E (Default)
F
SET
Flow Meter
TKS
Alarm
GPM
Programming
of
Relay
Set Point
Press
Step-6
Programming Relay Setpoint ON - OFF Options
Select - ALt.0, ALt.1, ALt.2, ALt.3,
ALt.0 (Default)
See Next Page for Relay Alarm Options-
F
SET
Flow Meter
TKS
Alarm
GPM
Programming
Relay
Time Delay
Press
Step-7
Programming Initial Start-Up Relay Time Delay
Range : 0-99 sec Delay Time to Power on Alarm Output Relay
t.20 (Default)
(20 Seconds)
Initial Start up of Flow Meter or Process (Allows for System
Steady State before Relay Switch becomes Active).
F
SET
Flow Meter
TKS
Alarm
GPM
Required when Programming Remote
Display or Controller
.
K-Factor Pre Programmed by Factory - No Flow Meter
Programming of a K-Factor is required.