Страница 1: ...he voltage applied is displayed according to the scale specified The relays remain energised while the input signal is between the upper and lower set points Once de energised the signal must change i...
Страница 2: ...lay for relay 2 St d 2 default 0 Sec max 100 0 Sec Reaction delay for relay 2 rE d 2 default 0 Sec max 100 0 Sec Relay 2 function rE F 2 default De energise Latch enable for Relay 2 LAt 2 default Enab...
Страница 3: ...pointer to the desired position SINGLE DISPLAY DEVICE PROGRAMMING Example 1 Set the device to de energise relay 1 when the voltage is below 10 0V and above 140 0V IfallofthefollowingsettingsareNOTavai...
Страница 4: ...ock parameters default unlocked Press BACK T then ENTER 4 and hold the 2 buttons until the desired option is displayed The display cycles between Loc no changes allowed u Loc parameters may be adjuste...