ONE-YEAR LIMITED WARRANTY
The Seller warrants its products against defects in material or workmanship for a period of one (1) year from the
date of manufacture. The liability of the Seller is limited, at its option, to repair, replace or issue a non-case credit for
the purchase prices of the goods which are provided to be defective. The warranty and remedies set forth herein
do not apply to any goods or parts thereof which have been subjected to misuse including any use or application
in violation of the Seller’s instructions, neglect, tampering, improper storage, incorrect installation or servicing not
performed by the Seller. In order to permit the Seller to properly administer the warranty, the Buyer shall: 1) Notify
the Seller promptly of any claim, submitting date code information or any other pertinent data as requested by the
Seller. 2) Permit the Seller to inspect and test the product claimed to be defective. Items claimed to be defective
and are determined by Seller to be non-defective are subject to a $30.00 per hour inspection fee. This warranty
constitutes the Seller’s sole liability hereunder and is in lieu of any other warranty expressed, implied or statutory.
Unless otherwise stated in writing, Seller makes no warranty that the goods depicted or described herein are fit for
any particular purpose.
LIAF022
Patent No. - Design: 424,953
Patent No. - Thermal Intrusion Barrier: 6,597,275
Patent Pending - SimpleSet
TM
Target Programming Technology
7313 William Barry Blvd., North Syracuse, NY 13212
(
Toll Free) 800-365-5525 (Phone) 315-233-5266 (Fax) 315-233-5276
www.icmcontrols.com
Operating Modes
These are the possible operating modes of the
SC2311L
.
Off Mode
In off mode, the thermostat will not turn on the heating or cooling appliances.
Note 2:
The indoor fan can be activated in every mode by sliding the Auto/On fan to the On
position.
Note 2:
Off mode in used to enter the configuration setup (by pressing
LEFT
and
RIGHT
simultaneously for 5 seconds).
Cool Mode
In cool mode, the thermostat controls the cooling system.
There is a four minute time delay after the compressor turns off. This protects the compressor.
Heat Mode
In heat mode, the thermostat controls the heating system.
For heat pumps, there is a four minute time delay after the compressor turns off. This protects the
compressor.
Emergency Heat Mode
(Heat pump systems only)
In emergency heat mode, the heat pump system will be disabled and auxiliary heat will become the
primary source of heat.
ENTER
Emergency heat mode by pressing the up button for ten seconds while in heat mode. “EH”
will then display on the screen.
EXIT
Emergency heat mode by pressing the up button for ten seconds. “EH” will not display on
the screen when you exit emergency heat mode.
The
SC2311L
also exits emergency heat mode when the mode switch is moved to Cool.
This feature is used for transferring the configuration settings from the master to the target
thermostat. All thermostats for a job can be mounted and powered up. Configure one thermostat. This
will be the master. The master will be used to copy the configuration to the rest of the thermostats.
Preparing the master to Send:
1. The master must be powered by 24 VAC.
2. Verify the master thermostat is in
OFF
mode. Slide system switch to center
position.
3. Remove cover of the master thermostat by gently pulling near one of the corners
at the top of the thermostat.
4. Press the
up
and
down
buttons and
LEFT
switch simultaneously for 5 seconds.
5. The
OUT
screen displays indicating the master thermostat is ready to
transfer data.
Note:
Press the
up
and
down
buttons and
LEFT
switch simultaneously for 5
seconds to exit from data transfer mode and to return the master to the
OFF
mode.
6. Connect the master to the target using the 3 wire connector. Attach one end to
the Master’s FP pins and the other end to the Target’s FP pins.
Note:
Target thermostat must be powered by 24 VAC for field programming
to occur.
When the connection has been made correctly, the master thermostat will power
up and the target will count from 6 down to 1. It will then display
LOC
confirming
the data has been saved in memory.
When all target thermostats have been completed, reinstall the master thermostat.
Press the
up
and
down
buttons and the
LEFT
switch simultaneously for 5 seconds to exit
from the data transfer mode and to return the master thermostat to the
OFF
mode.
SimpleSet
TM
Field Programming
FP Pins
SC2010 N/L
Lockout Feature
The
SC2311L
has a button lockout feature so the temperature adjustment is prohibited
or limited. Select the appropriate lockout from Configuration Mode Settings (Step 7) of
this guide.
To activate the LOC feature:
1. Simultaneously press the
LEFT, RIGHT
and
UP
buttons for 10 seconds.
2. LOC will display and the lockout function will be enabled.
To deactivate the LOC feature, repeat steps 1 and 2 above.
Troubleshooting
Symptom
Remedy
No display
Check for 24 VAC at thermostat; display is blank when 24 VAC is not
present
System fan does not come on
properly
Verify wiring is correct, check heat source configuration settings
(see Configuration Mode Setting 5)
All thermostat buttons are
inoperative
Verify 24 VAC is present; unit locks out when 24 VAC is not present
No response with first button press
First button press activates backlight only
Thermostat turns on and off too
frequently
Adjust temperature differential (see Configuration Mode Setting 2)
Fan runs continuously
Slide FAN switch to auto to turn fan off
Room temperature is not correct
Calibrate thermostat (see Configuration Mode Setting 10)
LOC displays when any button is
pressed
Thermostat has the button lockout function activated
(see Lockout Feature, and Configuration Mode Setting 7)
Heat or Cool not coming on
Verify wiring is correct, verify configuration settings are correct
Problem not listed above
Press Reset button once*
* Reset Button Function
: Configuration settings are unchanged and display is refreshed.
Starting the Thermostat
Room Temperature
CAUTION!
:
Do not use air conditioning when the outdoor temperature is below 50 degrees.
This can damage your air conditioning system and cause personal injuries.
1. Move the
Fan Auto/On
switch to the
Auto
position.
2. Move the
Cool/Off/Heat
switch to
Cool
or
Heat
, depending on the season.
Mode of Operation
The
SC2311L
is a two-stage heat, one-stage cool thermostat. It functions with air conditioning, heat
pumps, gas, oil or electric heat.
The thermostat activates the first stage heat when the room temperature is below the heat set
temperature (by the differential temperature). Second stage heat will be activated if the room
temperature continues to drop. The heat outputs are staged off as the room temperature increases.
For heat pump systems, the thermostat will not let the compressor come on for four minutes after it
turns off. This protects your compressor.
When the room temperature is greater than the cool set temperature (by the differential temperature),
the cooling device is activated. The cool output is turned off as the room temperature drops. The
thermostat will not let the compressor come on for four minutes after it turns off. This protects your
compressor.
The
SC2311L
has the following operating modes: OFF, Heat, Emergency Heat, and Cool. In OFF
mode, the thermostat will not turn on heating or cooling devices. In the Heat mode, the thermostat
controls the heating system. For heat pump systems, Emergency Heat mode is used to bypass
the compressor (only backup heat operates). In the Cool mode, the thermostat controls the cooling
system. The indoor fan can be turned on in all operating modes using the Fan switch.
Fan Test
1. Slide
Fan
switch to
On
position.
2. Indoor fan turns on.
Auto
On
Auto
On
3. Slide
Fan
switch to
Auto
position.
4. Indoor fan turns off.
Once the thermostat is installed, it should be thoroughly tested.
CAUTION!
:
Do not energize the air conditioning system when the outdoor temperature is
below 50 degrees. It can result in equipment damage or personal injury.
Testing the Thermostat
Cool Test
1. Slide
Mode
switch to
Cool
mode.
2. Adjust set temperature so it is 5 degrees below room temperature.
3. Air conditioning should come on within a few seconds.
4. Adjust the set temperature 2 degrees above the room temperature and the A/C should turn off.
There may be a fan delay on your system.
Note:
There is a four minute time delay to protect the compressor after it turns off. To
temporarily bypass the four minute delay, slide the
Mode
switch to
OFF
for 2 seconds
and then back to
Cool
.
Cool Off Heat
Heat Test
1. Slide
Mode
switch to
Heat
mode.
2. Adjust the set temperature so it is 5 degrees above the room
temperature.
3. Heat should come on within a few seconds.
4. Adjust the set temperature so it is 2 degrees below the room
temperature and the heat should turn off. There may be a fan delay on your system.
Note:
There is a four minute time delay to protect the compressor after it turns off. To
temporarily bypass the four minute delay, slide the
Mode
switch to
OFF
for 2 seconds
and then back to
Heat
.
Cool Off Heat