The configuration mode is used to set the SC2210 to match your heating/cooling system. The SC2210 functions with up
to 3-stage heat pump systems.
To configure the SC2210, perform the following steps:
1. Slide the
Mode
switch to the
OFF
position.
2. Remove the cover of the thermostat by gently pulling on one of the corners.
3. Simultaneously hold the
SW5
and
SW6
buttons in for 5 seconds while the SC2210 is in
OFF
mode.
4. Press the or button to change settings within each screen.
5. Press the
SW6
button to advance to the next screen.
Note:
The
SW5
button will return you to the previous screen.
6. To exit configuration mode, slide the
Mode
switch to
Heat
or
Cool
.
Configuration Mode Settings
The setup screens for Configuration Mode are as follows:
1.
Temperature Scale (F or C) –
Choose Fahrenheit or Celsius.
Press the or button to select.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
FILTER
DIFF
ROOM
SET
REMOTE
3.
Temperature Differential – Stage 2 – (1°F to 6°F) (0.5°C to 3.0°C) –
Set the number of degrees between when stage 1 turns on and stage
2 turns on.
Press the or button to set differential value.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
FILTER
DIFF
ROOM
SET
REMOTE
2.
Temperature Differential – Stage 1 – (1°F to 3°F) (0.5°C to 1.5°C) –
Set the number of degrees between your “setpoint” temperature and
your “turn on” temperature for first stage.
Press the or button to set differential value.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
Configuration Mode