ICM Controls ICM493-60A Скачать руководство пользователя страница 2

7313 William Barry Blvd., North Syracuse,  NY  13212

(Toll Free) 800-365-5525     (Phone) 315-233-5266 

(Fax) 315-233-5276

www.icmcontrols.com

ONE-YEAR LIMITED WARRANTY

The Seller warrants its products against defects in material or workmanship for a period of one (1) year from the date of manufacture. 

The liability of the Seller is limited, at its option, to repair, replace or issue a non-case credit for the purchase prices of the goods which 

are provided to be defective. The warranty and remedies set forth herein do not apply to any goods or parts thereof which have been 

subjected to misuse including any use or application in violation of the Seller’s instructions, neglect, tampering, improper storage, 

incorrect installation or servicing not performed by the Seller. In order to permit the Seller to properly administer the warranty, the Buyer 

shall: 1) Notify the Seller promptly of any claim, submitting date code information or any other pertinent data as requested by the Seller. 

2) Permit the Seller to inspect and test the product claimed to be defective. Items claimed to be defective and are determined by Seller 

to be non-defective are subject to a $30.00 per hour inspection fee. This warranty constitutes the Seller’s sole liability hereunder and 

is in lieu of any other warranty expressed, implied or statutory. Unless otherwise stated in writing, Seller makes no warranty that the 

goods depicted or described herein are fit for any particular purpose.

Parameter

Description

Range

Default Recommended

Line voltage

The expected line voltage

200-240

240

Nameplate voltage**

Over/under voltage The allowed percentage over and under the set line voltage

5% to 10%

10%

10% over/under

Anti-short delay

The amount of time delay between the end of a fault, and closing of the contactor 0:30 to 10:00

0:30

4 minutes

Reset mode retries The number of retries after a fault has occurred. Auto has unlimited retries.

1 to 5, Auto

Auto

Auto

Allowed MOV fail

The number of surge devices allowed to fail while maintaining operation. Setting 

to “5” will allow operation, even when surge protection has been exhausted.

0 to 5

5

Set to “5” for ensured operation.  Set to “4” for 

max. operation while ensuring surge protection.

Specifications

** For best recommendations, consult manufacturer of equipment.

Specifications

Input:  

Contact Ratings:

• 195-264 VAC 

• Voltage: 240 VAC

• 50/60 Hz 

• FLA: 60A

  

• 

LRA: 360A

Control Operating Temperature:

•  Operating temperature: -40°F to 167°F (-40°C to 75°C)

•  Storage temperature: -40°F to 185°F (-40°C to 85°C)

•  LCD operating temperature: -4°F to 167°F (-20°C to 75°C)
Mechanical:

• Mounting: Four mounting holes in back of enclosure

• Enclosure: NEMA/Type 3R, rain-tight enclosure rated for outdoor 

installation

Setting the Parameters

1.  Press the 

 button to scroll through various user-conFig.urable settings.

2.  Use the     buttons to change the set point. 
3.  When the last parameter has been set, you will return to the read screen.

LIAF277-1

• Dimensions: 8”L x 10”W x 6”H
Parameters:

•  Line voltage: 200-240 VAC, adjustable

•  Over/under voltage setting: 5%-10%, adjustable 

 

(under voltage limited to 195 VAC)

•  Anti-short cycle time delay: 0.5-10 minutes

•  Number of trials: 1-5, auto

•  Number of movistors: 0-5

Button Functions

Press to enter setup mode, and to toggle through user-conFig.

urable settings.

Press at any time to return to the Read screen, which will display 

any faults, the current line voltage, and the number of remaining 

MOVs.

Press to scroll through past recorded faults. Hold for 5 seconds to 

clear fault memory.

Hold for 2 secs. to reset unit.

Press to adjust settings   &  . Hold for 2 seconds to enter line 

voltage calibration.

Calibration Feature

The ICM493-60A can be calibrated to match the reading from a true RMS meter.
1. Measure input voltage from T1 to T2 using a true RMS meter.
2. Hold     buttons simultaneously until line voltage starts to flash.

3. Adjust voltage using   or   buttons to match measured voltage from step 1.
4. Push   button to lock values into memory.