Fault Conditions

Only

 swap phases during initial setup, 

not

 after the ICM450 has been in operation without 

errors.

Press and release fault button to scroll through all saved faults.

 

Note:

 For initial setup, press and hold FAULT for 5 seconds to 

remove any previously stored faults.

Fault

Problem

Corrective Action

Back 

Phase 

Loss

Not all three of the 
phases on the load side 
are present

1.  Re-energize the contactor.
2.  If the fault reappears after the load energizes:
  a.  Turn all power OFF
  b.  Check all load side connections
  c.  Check the contacts of the contactor for debris 

or excess carbon.

Back 

Phase 

Rev

Loads 1, 2, or 3 are not 
in sequence (not 120º 
phase shifted)

1.  Turn OFF all power.
2.  Swap any 2 phases on the load side of the 

ICM450 only (example: swap load 1 and load 2) *

3.  Re-apply power.

Back 

Phase 

Unbal

A voltage unbalance 
between the three load 
phases exceeds the 
unbalance setpoint

1.  Press the 

READ

 button to observe the present 

load voltages. Check system for unbalance cause.

2.  Increase the fault interrogation time if necessary.
3.  Increase the percent unbalance setting if 

necessary.

Front 

Over 

Volt

Average phase-phase 
voltage exceeds the 
maximum percentage

1.  Check system for over-voltage cause.
2.  Increase the percent over-voltage setting if 

necessary.

3.  Increase the fault interrogation time if necessary.

Front 

Phase 

Loss

Not all three of the 
phases on the line side 
are present

1.  Press and hold the 

READ

 button on the phase 

monitor or use an AC voltmeter to carefully 
measure all three phase-phase line voltages 
(example: Line 1   Line 2, Line 2   Line 3, Line 
3   Line 1).

2.  Repair the missing phase.

Front 

Phase 

Rev

Lines 1, 2, or 3 are not 
in sequence (not 120º 
phase shifted)

1.  Turn OFF all power.
2.  Swap any 2 phases on the line side of the ICM450 

(example: swap load 1 and load 2)*

3.  Re-apply power.

Front 

Phase 

Unbal

A voltage unbalance 
between the three line 
phases exceeds the 
unbalance setpoint

1.  Press the 

READ

 button to observe the present 

load voltages. Check system for unbalance cause.

2.  Increase the fault interrogation time if necessary.
3.  Increase the percent unbalance setting if 

necessary.

Front 

Under 

Volt

Average phase-phase 
voltage is below the 
minimum percentage

1.  Check system for under-voltage cause.
2.  Increase the percent under-voltage setting if 

necessary.

3.  Increase the fault interrogation time if necessary.

Содержание ICM450

Страница 1: ...American made products plus wiring diagrams troubleshooting tips and more visit us at www icmcontrols com ICM 450 Programmable Three Phase Voltage Monitor with 25 Fault Memory Protects motors from pre...

Страница 2: ...Parameters Installation of the ICM450 shall be performed by trained technicians only Adhere to all local and national electric codes Disconnect all power to the system before making any connections Ca...

Страница 3: ...is optional unit may be used to monitor line side only Wire the contactor and optional control voltage monitoring as in Figures 2 and 3 below Note Load line wire must be rated for 3 phase voltage rati...

Страница 4: ...hrough setup by pressing and releasing the SETUP button 4 When the last parameter has been set the phase average will be displayed and the Setup LED will automatically turn OFF Setting the Parameters...

Страница 5: ...Mode AUTO or number of times the load can be re energized after a load side fault before a manual reset is necessary Note When monitoring line side only the reset mode will always be AUTO AUTO 0 10 A...

Страница 6: ...nce setting if necessary Front Over Volt Average phase phase voltage exceeds the maximum percentage 1 Check system for over voltage cause 2 Increase the percent over voltage setting if necessary 3 Inc...

Страница 7: ...the faults press and hold FAULT for more than 5 seconds Load will not de energize when control voltage is OFF Phase Avg Load LED On Control LED Off The control mode setting is OFF press SETUP to get t...

Страница 8: ...r In order to permit the Seller to properly administer the warranty the Buyer shall 1 Notify the Seller promptly of any claim submitting date code information or any other pertinent data as requested...

Отзывы: