ICM Controls ICM326HN Скачать руководство пользователя страница 2

7313 William Barry Blvd., North Syracuse,  NY  13212

(

Toll Free) 800-365-5525     (Phone) 315-233-5266     (Fax) 315-233-5276

www.icmcontrols.com

ONE-YEAR LIMITED WARRANTY

The Seller warrants its products against defects in material or workmanship for a period of one (1) year from the date of 
manufacture. The liability of the Seller is limited, at its option, to repair, replace or issue a non-case credit for the purchase 
prices of the goods which are provided to be defective. The warranty and remedies set forth herein do not apply to any goods 
or parts thereof which have been subjected to misuse including any use or application in violation of the Seller’s instructions, 
neglect, tampering, improper storage, incorrect installation or servicing not performed by the Seller. In order to permit the 
Seller to properly administer the warranty, the Buyer shall: 1) Notify the Seller promptly of any claim, submitting date code 
information or any other pertinent data as requested by the Seller. 2) Permit the Seller to inspect and test the product claimed 
to be defective. Items claimed to be defective and are determined by Seller to be non-defective are subject to a $30.00 
per hour inspection fee. This warranty constitutes the Seller’s sole liability hereunder and is in lieu of any other warranty 
expressed, implied or statutory. Unless otherwise stated in writing, Seller makes no warranty that the goods depicted or 
described herein are fit for any particular purpose.

LIAF045-1

The 

Cutout Speed

 dial adjusts the motor voltage range that determines 

the RPM level of the condenser fan. Set the 

Cutout Speed

 dial 

according to the type of motor you have.

Sleeve Bearing Motors:

Set the 

Cutout Speed

 dial to the middle of the sleeve bearing range. In 

this range, the motor can run down approximately 40-50% of the full line 
voltage, which allows sufficient RPMs for cooling and lubrication.

CAUTION!

With sleeve bearing motors, it is important not to 
adjust outside the sleeve bearing range or bearing 
failure may result.

Ball Bearing Motors:

Set the 

Cutout Speed

 dial to the 

MIN

 position in the ball bearing range. This position offers the greatest range of 

speed control. At the 

MIN

 setting the motor can run down to approximately 20-30% of the full line voltage.

 

Note:

 

After starting at the recommended settings for either sleeve or ball bearing motors, you can tune the cutout 
speed to achieve the desired results.

Setting the Cutout Speed

Setting the Hard Start Time

During the 

Hard Start

 mode, full voltage is applied to the motor during startup to 

overcome windmilling and to lubricate the bearings.

The position of the 

Hard Start

 dial determines the time period of the 

Hard Start

 

mode. The dial can be adjusted between 0.1 second and approximately 5 seconds.

Set the 

Hard Start

 dial according to the type of motor you have. If you have a 

ball 

bearing motor

, set the 

Hard Start

 dial to the 

MIN

 position. If you have a 

sleeve 

bearing motor

, set the 

Hard Start

 dial to the middle of the sleeve bearing range.

After you begin at the recommended setting, you can fine tune the hard start 
time within the recommended range for the type of motor you have.

It is recommended that you use the minimum possible hard start time to avoid 
blowing too much cold air over the condenser.

Hard Start

 mode is activated when line voltage is applied (or disconnected and reapplied). The 

Hard Start

 mode 

applies full voltage to the motor for the set time period. Afterwards, the motor speed is dictated by the temperature 
sensor(s).

Symptom

Problem

Unit fails to start

The sensor may not be connected or it is defective.

With the probe disconnected, use an ohmmeter to measure the resistance between 
the probe wires. It should match the chart in Appendix B. If you read an 

OPEN

 or 

SHORT

, replace the sensor.

Fuse and/or circuit blows

The unit has been mis-wired and may be permanently damaged.

The fan cycles from full 

ON

 to full 

OFF

 with little 

or no modulation

First turn 

OFF

 the power. Reapply power and confirm hard start operation. Reduce 

the hard start period to the minimum setting required to accelerate the fan. 
Excessive hard starting causes large pressure drops by moving too much cold air 
over the condenser.

Check position of heat pump select jumper.

Should the cycling persist, move the probe up several bends into the condenser to 
increase the sensitivity to condensing temperature.

Fine tune cutout adjustment.

The fan does not come 

on at all

Measure the line voltage between 

LINE 1

 and 

LINE 2

 to confirm that the line voltage 

is present.

Remove the thermistor probe from the terminal block and measure its resistance 
at ambient temperature. Compare your reading at the appropriate temperature in 
Appendix B to see if the actual resistance approximates the listed value. Next, hold 
the probe in your hand and confirm that the resistance decreases.

Place a temporary jumper across the 

S2

 or 

S3

 terminals. Fan should run at full 

speed. If it does, recheck probe connection and verify probe is operating correctly.

The high pressure switch 

trips off

Move the probe farther into the condenser where the temperature is higher. This will 
produce a higher fan RPM and decrease the head pressure.

Fine adjust the cutout and hard start settings.

Troubleshooting

Mounting a sensor into the condenser

 

vs. mounting it on the liquid line

When a sensor is mounted into the condenser, the control responds more rapidly to changes in head pressure than 
when it is mounted on the liquid line. This is especially true for high efficiency condensers.

When the sensor is mounted on the liquid line, the control responds more slowly and the result can be a fan that 
cycles on and off.

Therefore, whenever possible, it is preferable to mount the sensor in the upper 1/3 of  the condenser instead of 
mounting it on the liquid line. A spot on the condenser that is 100°F when the pressures are correct is ideal.

Appendix A

°C

°F

RESISTANCE (K

Ω

)

32°

32.7

41°

25.4

10°

50°

19.9

15°

59°

15.7

20°

68°

12.5

25°

77°

10.0

30°

86°

8.1

35°

95°

6.5

40°

104°

5.3

45°

113°

4.4

50°

122°

3.6

Temperature vs. Probe Resistance

Appendix B

ICM326HN Typical Installation

Condenser

Condenser

Condenser

Sensor

Sensor

Sensor

Fan

Motor

 2

Motor

 1

Control 

Circuitry

  This terminal 

to be used 

for 240 VAC

ICM

326

HN

 can

 mo

nito

r tw

o ad

ditio

nal c

ond

ens

ers

Reversing 

Valve for 

Heat Pump

Line

 1

Line

 2

Line

 2

ICM327HN Typical Installation

Condenser

Condenser

Condenser

Sensor

Sensor

Sensor

Fan

Motor

 2

Motor

 1

Control 

Circuitry

ICM

327

HN

 can

 mo

nito

r tw

o ad

ditio

nal c

ond

ens

ers

Reversing 

Valve for 

Heat Pump

Line

 1

Line

 2

Line

 2

Normal Function

With probe temperatures above 100°F, the control applies full voltage to the motor. The green light is illuminated (full 
speed LED).

With probe temperatures between 70°F and 100°F, the motor speed is proportional to the probe temperature. The 
yellow light is illuminated (variable speed LED).

When the motor starts at temperatures between 70°F and 100°F, it will hard start for the length of time dictated by 
the setting of the 

Hard Start

 dial. After the hard start time has elapsed, the motor speed is controlled by the probe 

temperature.

As the temperature being sensed decreases, the output voltage decreases. The output voltage may decrease to the 
determined cutout speed. Upon reaching the 

Cutout Speed

 dial setting, the output voltage will go to zero volts.

System restart occurs when the temperature exceeds 70°F.

With probe temperatures below 70°F, the motor remains off. The green light and the yellow light are off.

Heat Pump Bypass Operation

Heat Pump Bypass

 mode runs the fan at full speed when the system is operating in 

Heat

 mode. This moves as 

much air across the condenser coil as possible.

If the 

Heat Pump Select

 jumper is in the 

N.O.

 position and line voltage 

is present at

 the HP terminals, the motor 

will be brought to full speed.

If the 

Heat Pump Select

 jumper is in the 

N.C.

 position and line voltage 

is not present at

 the HP terminals, the 

motor will be brought to full speed. 

A separate relay is not needed.

Mode of Operation

Отзывы: