LIAF294-1

FEATURES

SPECIFICATIONS

ICM292A Gas Ignition Control Board

•  Control voltage: 24 VAC (18-30 VAC), 60 Hz

•  Line voltage: 115 VAC, 60 Hz

•  Power consumption: 0.3A plus gas valve current at 24 VAC

•  Operating temperature: -40°C (-40°F) to 75°C (176°F)

Timing

•  Pre-purge: 30 seconds

•  Trial for ignition: 7 seconds

•  Retries: Two groups of two, 30 seconds delay within 

the group and 3 minutes delay between 

groups

•  Lockout: 1 hour

•  Post-purge: 90, 120, 160 and 180 seconds

Inputs

•  Power: 24 VAC and COM

•  Thermostat interface: R, W, Y and G

•  System switches: Vent pressure and limit switches 

(main and over-temperature switches in series)

•  Flame Sensing

•  Heat blower OFF delay: SW1 toggle switch

Install New Control

1. Ground yourself. When handling circuit board, hold it by the edges.

2. Fasten circuit board with retaining screws.

3. Connect all line voltage, low voltage, and accessory wires.

4. Verify the sequence of operation.

Safety Considerations

Only trained personnel should install or service heating equipment. When working with heating 

equipment, be sure to read and understand all precautions in the documentation, on labels, and on 

tags that accompany the equipment. Failure to follow all safety guidelines may result in damage to 

equipment, severe personal injury or death.

Introduction

The ICM292A DSI gas ignition control replaces the following Rheem model: 62-24140-04. The 

ICM292A has incorporated LED diagnostics to assist in troubleshooting. Fault code information can 

be found in this application guide. Please keep this application guide with the furnace installation 

manual for future reference.

Electrostatic Discharge (ESD) Precautions

CAUTION!

Use caution when installing and servicing the furnace to avoid and control electrostatic discharge; 

ESD can impact electronic components. These precautions must be followed to prevent 

electrostatic discharge from hand tools and personnel. Following the precautions will protect the 

control from ESD by discharging static electricity buildup to ground.

1. Disconnect all power to the furnace. Do not touch the control or the wiring prior to discharging your 

body’s electrostatic charge to ground.

2. To ground yourself, touch your hand and tools to a clean, metal (unpainted) furnace surface near 

the control board.

3. Service the furnace after touching the chassis. Your body will recharge with static electricity as you 

shuffle your feet or move around, and you must reground yourself.

4. Reground yourself if you touch ungrounded items.

5. Before handling a new control, reground yourself; this will protect the control. Store used and new 

controls in separate containers before touching ungrounded objects.

6. ESD damage can also be prevented by using an ESD service kit.

A W call from the thermostat will engage the Inducer Draft motor. The Vent Pressure switch closes. 

Ignition sequence begins, gas valve and spark are engaged, providing that system safety switches 

(Main and Over-temperature switches in series) are closed. The Blower motor will engage at HEAT 

speed 20 seconds after flame is established and sensed. On W call satisfaction, the Inducer motor 

turns off after 10 seconds and Blower motor turns off according to Heat Blower Off delay setting.
A G call from the thermostat will engage Blower motor without delay at FAN speed. It disengages 

without delay when G call is removed. 
A Y call from the thermostat will engage Blower motor without delay at COOL speed. It disengages  

45 seconds after Y call is satisfied.

Sequence of Operation

Flame not established

1. If flame is not established during the 7 second initial sequence then the control will start the next 

trial for ignition in 30 seconds.

2. There will be two more attempts to ignite after 3 minute delay, 30 seconds apart before the 

respective fault code is triggered and ignition trials are stopped.

3.  The gas valve is energized only during the ignition sequence of 7 seconds.

4. Blower motor is off until 20 seconds after flame is established.

Flame out

1. Flame out is considered when flame is lost during heating. 

2. When W signal is present and flame is not sensed, then gas valve will disengage until the next trial 

for ignition

3. If flame is not established on the immediate sequence (2 above) then the control will continue with 

additional trials for ignition

4. Inducer and Blower motors will continue running during flame out scenario 

Flame out of sequence

1. Flame out of sequence represents a scenario when flame is sensed while W signal is not present.

2. Inducer and Blower motors will be engaged (if not already running) and keep running for as long as 

the fault condition is present.

3. There is 1 hour lockout before a W call can be executed or on power reset

Troubleshooting Tips

LED Fault Codes

•  Direct Spark Ignition (DSI) control board
• Microprocessor-based
•  Controls inducer motors, air cleaner (if equipped), humidifier  

(if equipped), spark ignitor and the gas valve

•  Monitors timing, trial for ignition, system switches, flame sensing 

and lockout

•  100% lockout safety feature
•  Compatible with LP or natural gas
•  LED indication for status and fault codes to aid in troubleshooting
•  Replaces: Rheem 62-24140-04

LEDS

Flashes

Fault condition

GREEN

ON

Normal operation

1 Flash

Ignition failure (4 trials)

2 Flashes

Pressure switch stuck open

3 Flashes

Limit switches open

4 Flashes

Pressure switch stuck closed

5 Flashes

Twin fault

6 Flashes

Brownout voltage

7 Flashes

Hot and neutral reversed or no ground

Continuous Gas valve relay short

YELLOW

Rapid Blink Flame out of sequence
Slow Blink

Low flame or no flame

ON

Flame present

CAUTION!

To service control, and prior to disconnection, label all wires. Failure to do so may result in wiring 

errors that can cause dangerous operation.

Remove Existing Control

1. Turn thermostat to OFF position or set it to the lowest possible setting.

2. Turn OFF electrical supply to furnace.

3. Turn OFF gas supply to furnace.

 CAUTION: Failure to turn off gas and electric supplies can result in explosion, fire, death, or 

personal injury.

4. Remove furnace blower and control access doors.

5. Disconnect thermostat wires and humidifier wires (if equipped with a humidifier).

6. Disconnect line voltage, blower, electronic air cleaner wires (if equipped), and transformer wires.

7. Remove screws and any other fasteners, and the old circuit board.

8. Examine control and control box to check for water stains.

9. Make repairs if any sources of water leakage are found. Be sure to check humidifiers, evaporator 

coils, and vent systems in the area of the control.

Outputs 

•  Gas Valve:  

 

 

3A Pilot Duty @ 120 VAC

•  Draft Inducer Motor:  

 

3A max., 1/6HP @ 125 VAC

•  Cool Blower:  

 

 

16A max., 1/2HP @ 277 VAC

•  Heat Blower:  

 

 

14A max., 1/2HP @ 277 VAC

•  Circulating Fan: 

12A max., 1 HP @ 125 VAC

•  Heat/Cool Fan:  

 

10 A max., 1/2 HP @ 277 VAC

•  Electronic Air Cleaner:    

10 A max., 1HP @ 125 VAC

•  Humidifier:  

 

 

11 A max., 1/6HP @ 125 VAC

LED indicators

• Power, green LED:  PWR

• Status, green LED: OK

• Flame status, yellow LED: FLAME