General information
9
CONTROL PANEL
The control panels which can be installed on
REX
boilers are mentioned in the table.
They must be ordered separately from the boiler and for to their technical and installation characteristics refer to the manual
provided with the panel.
To choose the most appropriate control panel for the system refer also to the
CATALOGUE
, and to use it refer to the manual
supplied with the control panel.
Description
Code
Thermostatic control panel
QACC10ELMCE
eterm
boiler control panel
QETERM01CE
eterm
system control board
QETERM02
BURNERS
The burners that can be installed on the
REX
boilers must be CE marked according to European Directives:
–
European Regulation on Gas Equipment GAR 2016/426/EU
–
Electromagnetic Compatibility Directive 2014/30/EU
–
Low Voltage Directive 2014/35/EU
–
Machinery Directive 2006/42/EC (for liquid fuel burners)
They must also be able to operate on boilers with flame inversion combustion chamber.
Since the optimal operation of the boiler depends on the correct selection of the burner and its adjustment, find below some
points to take into account:
–
The firing range of the burner must include the boiler operating point (flow-back pressure in combustion chamber
considering the pressure at the base of the chimney as ZERO)
–
the length of the combustion head must be adequate to the penetration into the combustion chamber provided by ICI and
shown in the table
–
the length and shape of the flame must be suitable to the flame inversion combustion chambers. The burner manufacturers
have this information as they are required by certification.
Øb
P6
Description
U/M
REX
140
160
180
200
240
300
350
Øb
mm
320
320
320
360
360
400
400
P6
mm
350-400
350-400
450-500
450-500
450-500
450-500
450-500