iceqube MINI MAX Скачать руководство пользователя страница 2

Field Programming Guide MiniMax 3-2013 Rev.0 

2

Celsius) below this temperature.  Press the 

“+” 

or 

“-“

 key pads 

to change the alarm setpoint within a range of 8ºF (or 4ºC) 
above the set temperature “HI” set point, to 135°F (or 57°C). 

 

Press the 

“Select

” button to continue.  The set alarm “LO” LED 

is 

on

 with the display indicating the low temperature alarm set 

point.  The alarm will activate at this temperature and will 
automatically reset at two degrees Fahrenheit (or one degree 
Celsius) above this temperature.  Press the 

“+” 

or 

“-“

 key 

pads to change the alarm setpoint within a range of 8ºF (4ºC) 
below the set temperature “LO” set point, to 34°F (or 1° C). 

 

 

Press the “

Select”

 button to continue.  The alarm LED will 

flash and the display will show “ALL”, indicating the “ALL” 
alarm on/off status.  Press 

“Select

” and the display will show 

either “

ON”

 or “

OFF”, 

indicating current alarm status.  Press 

the 

“+” 

or 

“-“ 

key pads to toggle the mode as desired.  If the 

OFF”

 mode is selected, no alarms will activate and the audible 

on/off select function is skipped. 

 

Press the 

“Select

” button to continue.  The audible LED will 

flash and the display will show “

AUD”,

 indicating the audible 

alarm on/off status.  Press “

Select” 

and the display shows

 

ON”

 or “

OFF”

 indicating the current audible alarm status.  

Press the 

“+

” button or the 

“-

” button to toggle the mode as 

desired. 

 

Press the “

Select”

 button to continue.  The “C” LED flashes 

and the display shows either “

F”

 for degrees Fahrenheit or “

C”

 

for degrees Celsius.  Press the 

“+

” button or the 

“-

” button to 

toggle the mode as desired. 

 

Press the 

“Select

” button to continue.  The code LED is on 

and the display shows “PIN”.   To set a new user PIN code, 
press the “

+”

 button.  The display will flash “4”, prompting an 

entry of a four button sequence using the 

“+”, “-”, “Select” 

and/or

 “Exit” 

buttons.  (Any sequence of the four buttons may 

be programmed as the code.)  As the buttons are pressed, the 
display will show the number of buttons that were pressed. 

 

NOTE:  After pressing a button, there will only be 

5 seconds to press the next button.  If the 
next button is not pressed within the 
allotted time, the system will default to no 
PIN code, indicated by “0” on the display.  
Once the sequence is entered the display 
will no longer flash, and will show “4”. 

 

To program the no PIN code mode, press 

“-

” and the display 

will show “0”, indicating no PIN code.  With no PIN code, 
pressing any button will permit access to the program. 

 

*** CAUTION *** 

Always record the selection sequence (PIN code) and store in 

a secure place. 

 

Press the 

“Select

” button to continue.  The filter LED flashes 

and the display will show “

FIL”

, indicating the filter alarm days 

selection.  Press the 

“Select”

 button and the display will show 

the number of days that the alarm is set in one-half day 
increments.  (Example:  10.5 indicates the alarm will activate 
every ten and one-half days).  
Press the 

“+” 

or the 

“-

” key pads to vary the desired number of 

days.  (Range is 0-99 days). Programming 0 days will disable 
the alarm. 

 

NOTE:  The required number of days to set this 

alarm will be determined by the ambient 
air conditions.  If rain or wash down 

hoods are installed on the system, no 
filter is supplied and the filter alarm 
should be set to “0”.  This will disable the 
filter alarm

 

Press the 

“Select

” button to continue

.  

The program LED will 

be lit and the display will show 

“Add”.  

Press the 

“Select

” 

button again and a value of “

0.0”

 will appear

.  

Programming of 

the microprocessor is now complete.  
 
Press the 

“Select

” button to review all of the settings.  Press 

the 

“Exit

” button to enter the selected settings and to return to 

the normal operating mode.   

 

NOTE:  If the “Exit” button is not pressed, any 

changes to the program settings will not 
be saved. 

 

ALARM OPERATION

 

1. 

The enclosure temperature is above or below the 
alarm setpoint

 

The alarm LED will light, the display flashes, either “HI” or 
“LO” LEDs flash with the display and the audible alarm 
sounds (if activated).  The enclosure temperature must 
rise or fall two degrees Fahrenheit (one degree Celsius) 
before the alarm will reset. 

 

2. 

The condenser temperature is above the condenser 
alarm setpoint

 

The alarm LED lights, the display flashes the condenser 
temperature, and the audible alarm sounds (if activated).  
The condenser temperature must fall four degrees 
Fahrenheit (two degrees Celsius) before the alarm will 
reset.  

The above alarms can be manually reset by 

entering the PIN code into the system. 

 

3. 

The filter day timer has expired

:

 

 

The alarm LED lights, the display flashes showing “

FIL”

the filter LED flashes with the display and the audible 
alarm sounds (if activated).  The filter alarm may be 
cleared by pressing “

Exit”. 

 

4. 

Sensor Malfunctions

 

i. 

E-O  - Evaporator sensor open 

ii. 

E-C  - Evaporator sensor shorted 

iii. 

C-O  - Condenser sensor open 

iv. 

C-C  - Condenser sensor shorted 

 

NOTE:  An alternating E-O … C-O display 

may indicate the sensor connector 
has become disconnected from the 
rear of the controller. 

 

 

 

 

 

 
 

Отзывы: