Application Guide - NP900 Series
176 (504
)
A996A
Table 3.2.16.9-119. Event codes of the VUB function instance 1 – 4.
In the register of the VUB function is recorded start, trip or blocked “On” event process
data. In the table below is presented the structure of VUB function register content. This
information is available in 12 last recorded events for all provided instances separately.
Table 3.2.16.9-120. Register content.
Date & Time
Event
code
Fault
type
Trigger
voltage
Fault
voltage
Prefault
voltage
Trip time
remaining
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
1280-
1477
Descr.
Start
average
voltage
Trip
-20 ms
averages
Start
-200 ms
averages
0 ms -
1800 s
1 - 8
3.2.17
N
EUTRAL VOLTAGE
U0>
(59N)
Neutral overvoltage function (NOV) is used for non-directional instant- and time delayed
earth fault protection for various applications including feeder, filter and machine
applications of utilities and industry. Each IED with voltage protection module has four
available instances of the function (U0>, U0>>, U0>>>, U0>>>>).
NOV -function measures constantly phase to ground voltage magnitudes and calculates
the zero sequence component. Neutral overvoltage protection is scaled to line- to line
fundamental frequency component level. In case line to line voltage of system is 100 V
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...