Application Guide - NP900 Series
167 (504
)
A996A
User settable variables are binary signals from the system. Blocking signal needs to reach
the IED minimum of 5 ms before the set operating delay has passed for blocking to be
active in time.
3.2.15.5
E
VENTS AND REGISTERS
The VJP function generates events and registers from the status changes of start, trip and
blocked. To main event buffer is possible to select status “On” or “Off” messages.
In the function, there are 12 last registers available. The triggering event of the function
(alarm, trip or blocked) is recorded with time stamp and process data values.
Table 3.2.15.5-115. Event codes of the VJP function.
In the register of the VJP function, is recorded start, trip or blocked “On” event process
data. In the table below is presented the structure of VJP function register content. This
information is available in 12 last recorded events for all provided instances separately.
Table 3.2.15.5-116. Register content.
Date & Time
Event
code
Fault type
Trip da meas
/ dataset
Trip da meas
/ dataset
Used SG
dd.mm.yyyy
hh:mm:ss.mss
9920-
9925
Descr.
L1(2), L2(3),
L3(1) and U4
Trip angle
difference
Alarm angle
difference
1 - 8
3.2.16
P
OSITIVE SEQUENCE OVER
-
AND UNDER VOLTAGE
U1>/<
(59P/27P/47)
Sequence voltage function (VUB) is used for instant- and time delayed voltage protection
for various feeder, machine, utility and industry applications. It is has positive- and
negative sequence over- and under voltage protection built in. Each IED with voltage
protection module has four available instances of the function. Function measures
constantly fundamental frequency components of phase to earth voltage magnitudes or
line- to line and neutral voltage magnitudes to calculate the positive or negative sequence
voltage. Used voltage is user selected. VUB protection is based on system line- to line
Event
Number
Event
channel
Event block name
Event
Code
Description
Event
Type
Alarm
Type
9920
155 VJP1
0 Block On
1
0
9921
155 VJP1
1 Block Off
0
0
9922
155 VJP1
2 Trip On
1
1
9923
155 VJP1
3 Trip Off
0
0
9924
155 VJP1
4 Alarm On
1
0
9925
155 VJP1
5 Alarm Off
0
0
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...