12
Figure 7: Standard Controller
To change the factory default settings, enter the programming code sequence below:
“1 Adjust-up”
arrow
“2 Adjust-down”
arrow
“3 Select”
“4 Exit”
After pressing the above sequence the program LED should illuminate along with three alternating flashing boxes
on the display face, indicating the code was accepted. If no selection is made within 1 minute, the controller returns
to the normal operating mode.
Note: Pressing the “4 Exit” button at any time while in the programming mode returns the controller to the
normal operating mode.
Press
“3”
to continue programming. The set temperature “HI” LED illuminates with the display indicating the
“Cooling On” Set-point. The compressor will begin operation at this temperature and will remain operating until the
enclosure temperature decreases approximately 7°F (4°C). Press
“1”
or
“2”
until the desired set-point is displayed.
The range for this adjustment is 70° to 126°F (21° to 52°C). When the adjustment is complete, press
“3”
to
continue.
The set temperature “LO” LED is on with the display indicating the optional “Heating On” set-point. The heating
system will begin operation at this temperature and remain operating until the enclosure temperature increases
approximately 7°F (4°C). Press
“1”
or
“2”
until the desired set point is displayed within a range of 0°F to 63°F (-
17.8°C to +17°C).
Notes: Heat is only available with Ordinary Location Units
Notes: Review alarm settings if the “Cool On” or “Heat on” set-points have been changed.
Press
“3”
to continue. The set alarm “HI” LED is on with the display indicating the high temperature alarm set-
point. The alarm will activate at this temperature and will automatically reset at 2°F (1°C) below this temperature.
Press
“1”
or
“2”
to change the alarm set-point within a range of 8°F (4°C) above the set temperature “HI” set-point,
to 131°F (55°C).
Press
“3”
to continue. The set alarm “LO” LED is on with the display indicating the low temperature alarm set
point. The alarm will activate at this temperature and will automatically reset at 2°F (1°C) above this temperature.
Press
“1”
or
“2”
to change the alarm set-point within a range of 8°F (4°C) above the set temperature “LO” set-point,
to -20°F (-29°C).
Press
“3”
to continue. The “Alarm” LED will flash and the display will show “ALL” indicating the “ALL” alarm
on/off status. Press
“3”
and the display will show either “ON” or “OFF”, indicating current alarm status. Press
“1”
or
“2”
to toggle the mode as desired. If the “OFF” mode is selected, no alarms will activate and the audible on/off
select and POA, Power Off Alarm, functions are skipped.
Содержание Evolution Series
Страница 7: ...7 Figure 1 Enclosure Installation Figure 2 Push to Connect Fitting Ambient Side Enclosure Side...
Страница 9: ...9 Figure 4 Terminal Block Figure 5 Power Terminal Block...
Страница 17: ...17 Schematic Wiring Diagrams Ordinary Locations 120V 220V 230V Figure 8 IQ350942 Rev A...
Страница 18: ...18 Ordinary Locations 400V 460V 480V Figure 9 IQ350943 Rev A...
Страница 19: ...19 Hazardous Locations 120V 220V 230V Figure 10 IQ350921 Rev A...
Страница 20: ...20 Hazardous Locations 400V 460V 480V Figure 11 IQ350922 Rev A...
Страница 21: ...21 Specification Drawing 1000EV Figure 12...
Страница 22: ...22 2000EV Figure 13...
Страница 23: ...23 3000EV Figure 14...
Страница 24: ...24 4000EV Figure 15...
Страница 25: ...25 5000EV Figure 16...
Страница 26: ...26 6000EV Figure 17...
Страница 27: ...27 8000EV Figure 18...
Страница 28: ...28 10000EV Figure 19...
Страница 29: ...29 12000EV Figure 20...
Страница 30: ...30 14000EV Figure 21...
Страница 31: ...31 17000EV Figure 22...
Страница 32: ...32 20000EV Figure 23...
Страница 33: ...33 IQ1 2 3000EV Gasket and Cutout Same Gasket and Cutout for IQ1000EV IQ2000EV and IQ3000EV Figure 24...
Страница 34: ...34 IQ4 5 6000EV Gasket and Cutout Same Gasket and Cutout for IQ4000EV IQ5000EV and IQ6000EV Figure 25...
Страница 35: ...35 IQ8 10 12000EV Gasket and Cutout Same Gasket and Cutout for IQ8000EV IQ10000EV and IQ12000EV Figure 26...
Страница 36: ...36 IQ14 17 20000EV Gasket and Cutout Same Gasket and Cutout for IQ14000EV IQ17000EV and IQ20000EV Figure 27...
Страница 40: ...40 Notes...