background image

ELEVATION SERIES

REMOTE CONDENSER GUIDELINES

5

Remote Condenser Installation

For proper operation of the ice machine, the following installation guidelines must be followed. Failure to 

do so may result in loss of production capacity, premature part failure, and may 

void all warranties

.

Use the following for planning the placement of the remote condenser relative to the ice machine

Location Limits

Remote condenser location must not exceed 

ANY

 

of the following: 

Maximum rise from the ice machine to the

remote condenser is 35 physical feet.

Maximum  drop  from  the  ice  machine  to

the remote condenser is 10 physical feet.

Physical line set maximum length is 75 ft.

Calculated line set length maximum is 100

ft.

Ambient operating temperatures:                                

-20°F (-28.9°C) to 120°F (48.9°C)

Calculation Formula

Drop = dd x 6.6 

(dd = drop distance (ft.))

Rise = rd x 1.7 

(rd = rise distance (ft.))

Horizontal Run = hd 

(hd = horizontal distance (ft.))

Calculated Line Length = Drop + Rise + Horizontal Run

Configurations that do NOT meet these 

requirements must receive written authorization 

from Ice-O-Matic. This includes multi-pass or rack 

system remote condensers

DO NOT: Route a line set that rises, then falls, then

rises or a line set that falls, then rises, then falls

Remote Condenser Location

Pre-charged line sets are available in 25, 40, or 75

foot  length  to  connect  the  ice  machine  to  the

remote  condenser.  Select  the  best  available

location,  protecting  the  remote  condenser  from

extremes of dirt, dust and sun. Meet all applicable

building  codes.  The  services  of  a  licensed

electrician may be required.

Roof Attachment 

Install and attach the remote condenser to the roof

of the building using the methods and practices of

construction  that  conform  to  the  local  building

codes, including having a roofing contractor secure

the remote condenser to the roof. 

Have an electrician connect the remote condenser

fan  motor  wires  to  the  ice  machine  using  the

junction box at the back of the machine.

Pre-charged Line Set Routing

CAUTION: Do not connect the pre-charged tubing 

until all routing and forming of the tubing has been 

completed. See the coupling instructions for          

connecting information

Each  set  of  pre-charged  tubing  refrigerant  lines

consists of a 3/8 diameter liquid line and 1/2 inch

diameter  discharge  line.  Both  ends  of  each  line

have quick connect couplings, one end of the line

set has a Schrader valve connection.

Note: 

the openings in the building or ceiling or wall, 

listed in the next step, are the minimum sizes 

recommended for passing the refrigerant lines through.

Have a roofing contractor cut a minimum hole for

the  refrigerant  lines  of  2.50  inch.  Check  local

codes,  a  separate  hole  may  be  required  for  the

electrical power to the condenser. 

CAUTION: DO NOT KINK OR CRIMP 

REFRIGERANT TUBING WHEN INSTALLING 

IT

Содержание CIM0320

Страница 1: ...Ice O Matic 11100 East 45th Avenue Denver Colorado 80239 1 800 423 3367 9081484 01 REV R 4 2021 ELEVATION SERIES CUBE ICE MAKER CIM 300 lb through 2000 lb Cubers Installation Guide and Owner s Manual ...

Страница 2: ...vides this manual as an aid to the service technician in installation and maintenance of the CIM Series cube ice machines Do not attempt to perform installation start up or maintenance unless you have read and fully understand this manual Ice O Matic ice makers and dispensers are not approved for outdoor installation Air and water cooled ice machines are hermetically sealed and contain fluorinated...

Страница 3: ...xceeds 80 psi 5 5 bar a water pressure regulator must be installed All water supply lines must be installed per local codes Use 3 8 inch O D minimum on air cooled machines On water cooled machines 3 8 inch O D minimum tubing must be run to the condenser The water supply for the machine can T off from the condenser line using 3 8 inch O D minimum tubing Make 2 coils of extra tubing so that the mach...

Страница 4: ...rain line coming loose Silicone around the outer edge of the connection as needed to ensure a proper seal Clearance Requirements Self contained air cooled ice machines should have a minimum of 6 inches 15cm of clearance at the rear top and sides for proper air circulation and adequate space for serviceability Self contained air cooled ice machines exhaust air out of the top and right side of the u...

Страница 5: ... inch in all directions Check the water in the Water Sump for proper level Check the ice bridge for proper thickness Check the Water Regulating Valve adjustment if water cooled Secure the machine on top of the bin or dispenser Attach the ice machine to the bin with the mounting straps provided with the bin or dispenser Insure that the back of the ice machine is flush with the back of the bin Prope...

Страница 6: ...40 or 75 foot length to connect the ice machine to the remote condenser Select the best available location protecting the remote condenser from extremes of dirt dust and sun Meet all applicable building codes The services of a licensed electrician may be required Roof Attachment Install and attach the remote condenser to the roof of the building using the methods and practices of construction that...

Страница 7: ... makers incorporate the Mixing Valve in the condenser This configuration allows up to a 100 foot calculated remote line set run Reference the diagram on the next page to calculate the maximum 100 ft line set run Maximum actual line set run is limited to 100 ft The 75 foot line set will require 28 ounces of additional refrigerant Verify the CIM machine is compatible with the remote condenser For mo...

Страница 8: ...s Formula for maximum equivalent run RISE x 1 7 DROP x 6 6 HORIZONTAL RUN EQUIVALENT RUN NOT TO EXCEED 100 CALCULATED FEET Rise 35 ft x 1 7 40 ft 99 5 equivalent feet line run Drop 10 ft x 6 6 34 ft 100 equivalent feet line run 40 ft horizontal 35 ft rise 34 ft horizontal 10 ft drop ...

Страница 9: ... Hole for electrical connections 7 8 D Electrical junction box 7 8 CIM 2 W R Water Remote Cooled A Ice maker potable water in 3 8 FPT B Ice maker water out 3 4 FPT C Hole for electrical connections 7 8 D Electrical junction box 7 8 remote E Condenser water in 3 8 FPT water only Discharge line 1 2 male quick connect coupling for pre charged line set remote only F Condenser water out 1 2 FPT water o...

Страница 10: ... Hole for electrical connections 7 8 D Electrical junction box 7 8 CIM 3 W R Water Remote Cooled A Ice maker potable water in 3 8 FPT B Ice maker water out 3 4 FPT C Hole for electrical connections 7 8 D Electrical junction box 7 8 remote E Condenser water in 3 8 FPT water only Discharge line 1 2 male quick connect coupling for pre charged line set remote only F Condenser water out 1 2 FPT water o...

Страница 11: ...B Ice maker water out 3 4 FPT C Hole for electrical connections 7 8 D Electrical junction box 7 8 A Ice maker potable water in 3 8 FPT B Ice maker water out 3 4 FPT C Hole for electrical connections 7 8 D Electrical junction box 7 8 remote E Condenser water out 3 4 FPT water only Discharge line 1 2 male quick connect coupling for pre charged line set remote only F Condenser water in 3 8 FPT water ...

Страница 12: ...lusion of Anti Slush the unit will continue in freeze mode until the Low Water Float is satisfied closes indicating the formation of a full slab of Ice on the Evaporator and will start the harvest Cycle Harvest Cycle The Fan Motor shuts down as the Hot Gas Valve Purge Valve and Water Inlet Valve are energized The Water Inlet Valve will stay energized for additional time after the Purge Valve close...

Страница 13: ... above across the middle of the ice slab on the second batch produced The ice thickness can be changed on the Float Housing by turning the adjustment arm clockwise to decrease the bridge thickness and counter clockwise to increase the bridge thickness You will hear a click with each adjustment It is recommended adjustments be made one or two clicks at a time When a more substantial adjustment is n...

Страница 14: ...ss and adjustment procedure 3 Check water level in Sump See page 11 for proper water level and adjustment procedure 4 Clean the condenser air cooled machines to ensure unobstructed air flow 5 Check for leaks of any kind water refrigerant oil etc 6 Check the bin control switch if applicable for proper adjustment 7 Check the Water Regulating Valve water cooled machine for proper adjustment by measur...

Страница 15: ...ent diluted per manufacturer s instructions In addition for CIM models revision 4 and higher KAY 5 Sanitizer may also be used Please refer to www iceomatic com for approved chemical formulations and proper pH balance CAUTION Do not mix cleaner descaler and sanitizer together Eye protection is recommended when handling descaler or sanitizer Wear protective rubber gloves when handling descaler or sa...

Страница 16: ...ter spillway water distributor upper evaporator cover lower evaporator curtain and all splash surfaces Verify that all residue and residual minerals have been removed 16 If a full clean of water components is required this can be done by referring to the service manual for water system component breakdown This is recommended to be done by a qualified service agent 17 Re assemble all ice machine wa...

Страница 17: ...r machine looking like new 1 Clean the stainless steel and aluminum thoroughly once a week Clean frequently to avoid build up of hard stubborn stains Hard water stains left to sit can weaken the metals corrosion resistance and lead to rust or corrosion Use a nonabrasive cloth or sponge working with not across the grain 2 Do not use abrasive tools to clean the metal surface Do not use steel wool ab...

Страница 18: ...he frame let the back of sump fall downward 3 Similar to step 1 lift the front of the sump and push backward to allow the retaining features on the sump to clear the frame Push down towards the back until the sump is free from the frame Turn the sump sideways and remove it through the ice drop zone 4 To re install reverse steps 1 through 3 and tuck the water pump tube into the sump after the sump ...

Страница 19: ... evaporator s If ice is being made initiate harvest by pressing the Power Button for approximately 3 seconds The unit will shut off automatically following the harvest 3 Disconnect the tubing between the water pump discharge and water distribution tube and drain any water 4 On water cooled machines hold the water regulating valve open by prying upward on the water valve spring with a screwdriver w...

Страница 20: ...ing the plastic lampholder body and pulling away from the bulb Do not grip the lampholder by the connecting wires under any cir cumstances as this is a high voltage hazard The 4 pins on the pin end of the bulb will be exposed after disconnecting the lampholder 4 Push the bulb through the flat end of the end cap until approximately one inch of the bulb has moved through the pin end of the end cap 5...

Страница 21: ...bulb by inserting the flat end into the appropriate end cap 2 Reconnect the lampholder to the pin end of the bulb 3 Replace any access panels removed from the ice machine 4 Reconnect the power supply to the ice machine 5 Dispose of any old bulbs in accordance with all regulations pertaining to hazardous waste dis posal these bulbs contain small traces of mercury Visit lamprecycle org for informati...

Отзывы: