console water source heat pump (wshp)

5

operating & maintenance manual

 - 

console water source heat pump (wshp)

controlS

operating inStructionS & SeQuence 
oF operationS

 

 

 All standard 

ICE AIR WSHP

 units are 

 equipped with unit mounted digital controls. 

 (If your unit has optional wall mounted or 

 remote controls, see the separate operating 

 instructions supplied with those controls). 

 The standard controls are located under the 

 Air Discharge Grille at the top of the room 

 cabinet.  Lift the Access Door, located at the 

 right side of the Air Discharge Grille, to  

 access the control panel. 

 

ICE AIR WSHP

 console units are controlled 

 

by a state of the art electronic package that  

 

is comprised of a digital control pad and an 

 

internal Power Control Board (PCB). 

 

The large LCD display panel includes clearly 

 

marked control buttons. The Control pad is a 

 

programmable, user-friendly device that  

 

enables the user to program desired  

 

temperature settings and operational modes.

lcD programmaBle tHermoStat 

Feature liSt

• 

Operates on 2 stage Heat and 2 stage Cool 

• 

7 programs (Mo, Tu, We, Th, Fr, Sa, Su) or 

 

5-2 programs (Mo-Fr, Sa-Su) 

• 

4 Separate Time and Temperature Settings  

 

for each program

• 

Heat and Cool set-points for each program

• 

EPROM stores heat and cool program  

 

 

settings

• 

Temporary Program Override

• 

Permanent Program Override

• 

Compressor Short Cycle Protection

• 

LCD Backlighting

• 

Low Temperature Protection

 

uSer interFace

puSH ButtonS

symBol

press

holD

 

 s

up/override mode up/permanent  

override mode

  

t

Down/

override mod

e

Down/permanent 

override mode

on/oFF

on/oFF

--------

moDe

set operation 

mode

Internal setting

Fan

set fan speed/ 

confirm

--------

Содержание Console Water Source Heat Pump

Страница 1: ...Console Water Source Heat Pump WSHP OPERATING MAINTENANCE MANUAL World class comfort ...

Страница 2: ... 14 1 4 SECTION G G SCALE 1 10 HOLE FOR DRAIN HOSE JUNCTION BOX FRONT VIEW NOTES DIMENSIONS ARE SHOWN IN INCHES 1 OPTIONAL MOTORIZED WATER VALVE IS SHOWN 2 ALL DIMENSIONS ARE 1 4 3 LEFT HAND CONFIGURATION IS SHOWN 4 UNIT IS SHIPPED WITH UNIVERSAL LEFT HAND OR RIGHT HAND 5 PIPING CAPABILITY 6 OPTIONAL OUTSIDE AIR DOOR SHOWN 7 SUPPLY AND RETURN PIPES HAVE 1 2 THREADED FEMALE ADAPTER A B C D E 5HPW09...

Страница 3: ...ed in a separate instruction sheet specific to that option On behalf of ICE AIR and our network of distributors and dealers we are happy to welcome you to our base of satisfied customers CONSUMER SAFETY AND OPERATING NOTES FOR SAFE AND OPTIMAL ENJOYMENT OF YOUR ICE AIR WSHP UNIT PLEASE READ THE FOLLOWING CONSUMER SAFETY AND OPERATING NOTES CAREFULLY BEFORE OPERATING YOUR EQUIPMENT This unit MUST b...

Страница 4: ...circuit breaker for branch circuit overcurrent protection Consult the unit serial plate for current ratings All 208 230V units are wired for 208V operation unless otherwise specified The following physical conditions must be maintained for proper unit operation Unobstructed air flow into and out of the unit room enclosure cabinet Therefore Do not place furniture rugs or objects directly in front o...

Страница 5: ...Power Control Board PCB The large LCD display panel includes clearly marked control buttons The Control pad is a programmable user friendly device that enables the user to program desired temperature settings and operational modes LCD Programmable Thermostat Feature list Operates on 2 stage Heat and 2 stage Cool 7 programs Mo Tu We Th Fr Sa Su or 5 2 programs Mo Fr Sa Su 4 Separate Time and Temper...

Страница 6: ...perature The unit will cycle until the set temperature is achieved and then will continuously cycle to maintain the set temperature The temperature reading that is on constant display is the ambient room temperature EVENT TIME HEAT COOL MON FRI WAKE leave return SLEEP 6 00 AM 8 00 AM 6 00 PM 10 00 PM 70º F 21º C 62º F 17º C 70º F 21º C 62º F 17º C 78º F 26º C 85º F 29 5º C 78º F 26º C 82º F 28º C ...

Страница 7: ...an when complete The cool limit setting should be at least 4 F higher than the heat limit setting The cool limit setting is 55 F to 95 F The heat limit setting is 51 F to 91 F Exit Internal Setting and Return to Normal Mode 1 Press Fan to confirm and return to normal mode 2 If no key is pressed for 15 seconds it will return to normal mode automatically Temporary Program Override 1 When thermostat ...

Страница 8: ...anual assumes that your WSHP unit has been installed by a qualified installation professional and is operating properly prior to maintenance service Have your unit periodically inspected by a properly trained service professional or building maintenance staff person The unit should be checked for the safe and proper functioning of all of its systems at least once a year The following recommended m...

Страница 9: ...n a facility properly equipped to handle this type of work in a safe and professional manner Drain Pan Drain Hose Cleaning The condensate pan is located directly under the evaporator coil Check the visible section of the interior of the drain pan for any buildup of dirt or condensate water Wash annually to remove all dirt build up Check condensate drain pan for algae growth every 2 to 3 months If ...

Страница 10: ...east once a month Pay special attention to hose assemblies and connections Repair any leaks and replace deteriorated hose immediately to avoid potential costly damage to your property due to component failure TROUBLESHOOTING 1 If unit is not operating conduct the following checks If a flashing A appears on the display contact a trained technician Check the electrical connections Check the voltage ...

Страница 11: ...ed Normal Off On Off High Pressure Off Off Flash Low Pressure Flash Off Off Evaporator too cold Flash Off Flash Coaxial winter protection Flash on off Temperature probe failure Off flash Off High low voltage Off Off On Condensate over flow on Off Off Coaxial water too cold on Off flash troubleshooting error code menu ...

Страница 12: ...RES MUST BE SERVICED BY QUALIFIED TRAINED PERSONNEL ELECTRIC SHOCK HAZARD DISCONNECT FROM LIVE ELECTRIC CIRCUIT BEFORE SERVICING MOVING PARTS HAZARD DISCONNECT FROM LIVE ELECTRIC CIRCUIT BEFORE SERVICING UNIT MUST BE OPERATED WITH ALL CHASSIS SHEET METAL PARTS PROPERLY IN PLACE UNIT MUST BE OPERATED WITH ALL ENCLOSURE CABINET PARTS IN PLACE READ THIS ENTIRE OPERATIONS MANUAL BEFORE OPERATING THE U...

Отзывы: