operating & maintenance manual
–
console water source heat pump (wshp)
5
operating & maintenance manual
-
console water source heat pump (wshp)
controlS
operating inStructionS & SeQuence
oF operationS
All standard
ICE AIR WSHP
units are
equipped with unit mounted digital controls.
(If your unit has optional wall mounted or
remote controls, see the separate operating
instructions supplied with those controls).
The standard controls are located under the
Air Discharge Grille at the top of the room
cabinet. Lift the Access Door, located at the
right side of the Air Discharge Grille, to
access the control panel.
ICE AIR WSHP
console units are controlled
by a state of the art electronic package that
is comprised of a digital control pad and an
internal Power Control Board (PCB).
The large LCD display panel includes clearly
marked control buttons. The Control pad is a
programmable, user-friendly device that
enables the user to program desired
temperature settings and operational modes.
lcD programmaBle tHermoStat
Feature liSt
•
Operates on 2 stage Heat and 2 stage Cool
•
7 programs (Mo, Tu, We, Th, Fr, Sa, Su) or
5-2 programs (Mo-Fr, Sa-Su)
•
4 Separate Time and Temperature Settings
for each program
•
Heat and Cool set-points for each program
•
EPROM stores heat and cool program
settings
•
Temporary Program Override
•
Permanent Program Override
•
Compressor Short Cycle Protection
•
LCD Backlighting
•
Low Temperature Protection
uSer interFace
puSH ButtonS
symBol
press
holD
s
up/override mode up/permanent
override mode
t
Down/
override mod
e
Down/permanent
override mode
on/oFF
on/oFF
--------
moDe
set operation
mode
Internal setting
Fan
set fan speed/
confirm
--------